Programming Function Blocks and Features

 

 

 

 

 

 

 

Table 4-51 Totalizer Prompts

 

 

 

 

 

 

 

 

 

 

 

 

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

 

INPUT SOURCE

 

 

OFF, analog parameter,

 

 

Input source to be totalized.

 

 

 

 

 

 

number.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT LOW LIMIT

 

 

OFF or number

 

 

The range outside which the displayed output will flash

 

 

 

 

 

 

 

 

 

unclamped. Useful for warning operator of unusual

 

 

OUTPUT HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

condition.

 

 

 

 

 

 

 

 

 

 

 

 

 

ACTION

 

 

UP

 

 

At each machine scan cycle, an integration of the input is

 

 

 

 

 

 

 

 

 

added to the running total. When this total reaches or

 

 

 

 

 

 

 

 

 

exceeds the preset value (assumed to be in eng. Units), the

 

 

 

 

 

 

 

 

 

discrete output of the totalizer goes high and remains high

 

 

 

 

 

 

 

 

 

for 1 scan cycle. The totalizer then resets and starts again.

 

 

 

 

 

 

 

 

 

The value resets to either zero or the residual total (final

 

 

 

 

 

 

 

 

 

total minus preset) if one exists.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOWN

 

 

At each machine scan cycle, an integration of the input is

 

 

 

 

 

 

 

 

 

subtracted from the preset value. When this result reaches

 

 

 

 

 

 

 

 

 

or goes below zero, the discrete output of the totalizer goes

 

 

 

 

 

 

 

 

 

high and remains high for 1 scan cycle. The totalizer then

 

 

 

 

 

 

 

 

 

resets and starts again. The value resets to either the

 

 

 

 

 

 

 

 

 

preset or the residual total (preset plus final total [since final

 

 

 

 

 

 

 

 

 

total is either zero or negative]) if one exists.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEMAND

 

 

On Demand. Same as UP, except executes only while the

 

 

 

 

 

 

 

 

 

ON DEMAND INPUT discrete is ON(1). Input is ignored

 

 

 

 

 

 

 

 

 

while ON DEMAND INPUT is OFF(0).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTIN

 

 

Continuous. Same as UP except the total ignores the

 

 

 

 

 

 

 

 

 

PRESET value and integrates “forever” (continuously).

 

 

 

 

 

 

 

 

 

 

 

 

 

TIME UNITS

 

 

SEC, MIN, HOUR, DAY

 

 

Time units of the totalizer

 

 

 

 

 

 

 

 

 

 

 

ON DEMAND INPUT

 

 

OFF, discrete parameter, 0,

 

 

Appears for Functions as the On Demand input for the

 

 

 

 

 

1

 

 

DEMAND action. Activates totalizer when ON(1).

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESET

 

 

OFF, analog parameter,

 

 

Up totalizer counts up to this value. Down totalizer counts

 

 

 

 

 

 

number

 

 

down from this value.

 

 

 

 

 

 

 

 

 

 

 

 

 

ZERO CUTOFF

 

 

OFF or number

 

 

Represents the least value to be accumulated in the

 

 

 

 

 

 

 

 

 

totalizer. Input values below this value will be input as zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

RESETTABLE

 

 

YES, NO

 

 

If NO, the Totalizer is non-resettable and cannot be reset

 

 

 

 

 

 

 

 

 

via the operator keypad. This setting does not affect the

 

 

 

 

 

 

 

 

 

action of the reset discrete parameter.

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete parameter, 0,

 

 

When the RESET goes high (1) an UP action totalizer will

 

 

 

 

 

1.

 

 

reset to zero, or a DOWN action totalizer will reset to the

 

 

 

 

 

 

 

 

 

preset value. Use SY1 F3 to reset with the RESET or F3

 

 

 

 

 

 

 

 

 

key.

 

 

 

 

 

 

 

 

 

 

 

 