Honeywell VRX180 user manual Point Block Average 1 Pt Block Avg, 45 1 Point Block Average Prompts

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 152
Image 152

Programming Function Blocks and Features

1 Point Block Average (1 Pt Block Avg)

Outputs a block mean average CVn OV of the input over the specified Average Period. A new sample of the input will be taken on every instrument scan cycle. The block average is only updated at the end of the Average Period.

When the Reset Input is ON(1) all accumulated samples are discarded and the output is held until the Reset Input is OFF(0), then the averaging period resets.

Table 4-45 describes the 1 Point Block Average prompts. See Table 4-2 for additional prompts.

Table 4-45 1 Point Block Average Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output’s display limits. Output is not clamped or

 

 

 

 

 

 

 

 

flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog parameter,

 

 

This parameter will be averaged.

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete parameter, 0, 1

 

 

When the Reset is ON(1) all accumulated samples are

 

 

 

 

 

 

 

 

discarded and the output is held until the Reset is OFF(0),

 

 

 

 

 

 

 

 

then the averaging period resets.

 

 

 

 

 

 

 

 

 

 

 

AVERAGE PERIOD

 

 

0.1 to 1440

 

 

Length of averaging period in minutes.

 

 

 

 

 

 

 

 

 

 

138

Video Recorder – User Manual

Page 152
Image 152
Honeywell VRX180 user manual Point Block Average 1 Pt Block Avg, 45 1 Point Block Average Prompts, Average Period