Programming Function Blocks and Features

AO2 BC

UNITS = FPS

INPUT TYPE = LINEAR

DIRECT/INDIRECT/SQRT = SQRT

RANGE LOW = 0

RANGE HIGH = 40

CIRCUIT LOW = 1

CIRCUIT HIGH = 5

 

 

ELECTRICAL UNITS = VOLTS

FEEDBACK

 

 

AIR

P

 

AI2

AI2 OV

 

 

4 TO 20 mA

 

 

 

PV

 

 

SIGNAL

 

 

 

 

 

 

TO AIR FLOW

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

LP2

LP2 OV

VALVE

 

 

 

 

 

 

 

IN AO2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AI3 OV

WILD

 

+

 

 

VARIABLE

FUEL

P

AI3

 

 

 

 

 

 

 

SIGNAL

 

 

 

 

 

 

 

 

 

 

UNITS = FPS

 

 

 

 

RATIO

RATIO

 

 

 

SETPOINT

BIAS

INPUT TYPE = LINEAR

 

 

 

 

 

DIRECT/INDIRECT/SQRT = SQRT

TYPE = RATIO

 

RANGE LOW = 0

 

SETPOINT #1 = 500

 

RANGE HIGH = 40

 

 

CIRCUIT LOW = 1

 

WILD VARIABLE = AI3 OV

CIRCUIT HIGH = 5

 

RATIO SETPOINT = 0.50

ELECTRICAL UNITS = VOLTS

RATIO BIAS = 0.75

 

GAIN = 10

RESET = 1

RATE = 0

SP2

OUTPUT TYPE = CAT

 

IN LOW LIMIT = 0

 

IN HIGH LIMIT = 100

 

OUT LOW LIMIT = 4

 

OUT HIGH LIMIT = 20

Working set point of loop when use of WILD VARIABLE is desired to establish proper control of PV. If ratio control using WILD VARIABLE must be temporarily suspended, loop’s working

set point may be switched ON LINE to SETPOINT #1 via “SP (Set Point Select)” key on instrument’s front door.

Figure 4-1 Function Block Configuration of a Typical Ratio Control Loop

When the ratio control loop in Figure 4-1 is brought ON LINE, its ON LINE display must be accessed to allow the instrument’s SP (Set Point Select) key to be operational. To make the working set point of the ratio control loop equal the equation (WILD VARIABLE X RATIO SETPOINT) + RATIO BIAS, then select the TUNE LOOP menu item TOGGLE SETPOINT SOURCE so that an “SP2” is seen in the loop’s ON LINE display. Note that within the ratio control loop’s programming menu (accessed under PROGRAM CONTROL LOOPS), you will not find a SETPOINT #2 menu choice. The ratio control loop function block operates with the formula (WILD VARIABLE X RATIO SETPOINT ) + RATIO BIAS assuming all the functionality of the ratio loop’s second set point. Pressing the SP key to switch the working set point of a live ratio control loop from SP2 to SP1 will essentially suspend any ratio control and cause the loop to behave like a standard PID controller. This standard PID loop will have a local set point equal to the value programmed for SETPOINT #1. To control the process variable using a fixed set point that is independent of the loop’s WILD VARIABLE input, toggle the ratio control loop’s working set point to SP1.

100