Programming Function Blocks and Features

Table 4-49 CEMS Rolling Average Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output’s display limits. Output is not clamped or flashed

 

 

 

 

 

 

 

 

when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog

 

 

Input to be averaged.

 

 

 

 

 

parameter, number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete

 

 

When discrete is ON(1), average is reset to zero; when ON(1)-to-

 

 

 

 

 

parameter, 0, 1

 

 

OFF(0), average restarts.

 

 

 

 

 

 

 

 

 

 

 

TIME UNITS

 

 

Seconds, minutes,

 

 

Time units of the averaging period.

 

 

 

 

 

hours, or days.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AVERAGE PERIOD

 

 

OFF or number

 

 

Number of time units per average period.

 

 

 

 

 

 

 

 

 

 

 

FRAME PERIOD

 

 

OFF or number

 

 

Number of time units per Frame Period. Must divide evenly into

 

 

 

 

 

 

 

 

Average Period.

 

 

 

 

 

 

 

 

 

 

 

CALIBRATE HOLD

 

 

OFF, discrete

 

 

When ON(1), no samples are taken and the output is held.

 

 

 

 

 

parameter, 0, 1

 

 

If calibrate hold is set ON, the function block stops acquiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

samples; however, the averaging will continue to update for the

 

 

 

 

 

 

 

 

remainder of the average period, after which, the output value will

 

 

 

 

 

 

 

 

hold.

 

 

 

 

 

 

 

 

If calibrate hold is set ON longer than the average period, the

 

 

 

 

 

 

 

 

display will alternate between the last output value and

 

 

 

 

 

 

 

 

*****(indicating the current value is no longer valid).

 

 

 

 

 

 

 

 

If calibrate hold is set OFF and the CEM Rolling Average is not

 

 

 

 

 

 

 

 

reset, the CEM Rolling Average will continue to update every frame

 

 

 

 

 

 

 

 

period from the last value. If the CEM Rolling Average is reset, the

 

 

 

 

 

 

 

 

average value is set to zero and the displayed value will not update

 

 

 

 

 

 

 

 

until the Average period has transpired. The average value will

 

 

 

 

 

 

 

 

update every frame period.

 

 

 

 

 

 

 

 

 

 