Programming Function Blocks and Features

Loop Menu Items

Table 4-10 alphabetically describes every loop menu item. See Table 4-2 for additional prompts.

Table 4-10 Loop Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

APPROACH HIGH

 

 

Enter a value 0.1 to 100 or

 

 

This function affects the process variable approach to set

 

 

 

 

 

OFF.

 

 

point when the process variable value is less than the set

 

 

 

 

 

 

 

 

point value. The value entered is the percent of span

 

 

 

 

 

 

 

 

deviation from set point at which a recalculation of the

 

 

 

 

 

 

 

 

loop integral value will occur. Enter a starting value equal

 

 

 

 

 

 

 

 

to the proportional band value (1/gain value) x 100 if Gain

 

 

 

 

 

 

 

 

is used, or OFF at initial configuration. The value may be

 

 

 

 

 

 

 

 

altered Online for final loop tuning. This function is useful

 

 

 

 

 

 

 

 

for batch startup from a "cold" condition to control

 

 

 

 

 

 

 

 

excessive overshoot when set point is reached.

 

 

 

 

 

 

 

 

 

 

 

APPROACH LOW

 

 

Enter a value 0.1 to 100 or

 

 

Affects the process variable approach to set point when

 

 

 

 

 

OFF.

 

 

the process variable value is greater than the set point

 

 

 

 

 

 

 

 

value.

 

 

 

 

 

 

 

 

 

 

 

AUTO/MAN SELECT

 

 

OFF, discrete parameter, 0, 1

 

 

This parameter takes the place of the Auto/Man button

 

 

 

 

 

 

 

 

when the DISCR VS KEY SEL discrete is ON (1).

 

 

 

 

 

 

 

 

AUTO/MAN SELECT = ON(1) = Manual mode

 

 

 

 

 

 

 

 

AUTO/MAN SELECT = OFF (0) = Automatic mode

 

 

 

 

 

 

 

 

When DISCR VS KEY SEL is OFF(0), AUTO/MAN SEL

 

 

 

 

 

 

 

 

has no effect.

 

 

 

 

 

 

 

 

 

 

 

CHG ACTION INPUT

 

 

OFF, discrete parameter, 0, 1

 

 

Change Action Input. Selects the opposite control action

 

 

 

 

 

 

 

 

from that selected for the control action (see CONTROL

 

 

 

 

 

 

 

 

ACTION). Control action is opposite when the discrete

 

 

 

 

 

 

 

 

value is ON or "1".

 

 

 

 

 

 

 

 

 

 

 

CONTROL ACTION

 

 

Reverse (REV) or Direct (DIR)

 

 

When Reverse Acting Control is selected, the loop output

 

 

 

 

 

Acting Control.

 

 

will increase as the process variable becomes less than

 

 

 

 

 

 

 

 

set point, and will decrease as it becomes greater than

 

 

 

 

 

 

 

 

the set point. When Direct Acting Control is selected, the

 

 

 

 

 

 

 

 

output action is opposite.

 

 

 

 

 

 

 

 

 

 

 

DISCR VS KEY SEL

 

 

OFF, discrete parameter, 0, 1

 

 

Discrete vs. Keyboard select. When this discrete is ON

 

 

 

 

 

 

 

 

(1), the Auto/Man and Set point buttons are disabled; their

 

 

 

 

 

 

 

 

functioning is transferred to the AUTO/MAN SELECT and

 

 

 

 

 

 

 

 

SETPOINT SELECT discretes. See AUTO/MAN SELECT

 

 

 

 

 

 

 

 

and SETPOINT SELECT. Status changes made by

 

 

 

 

 

 

 

 

AUTO/MAN SELECT and SETPOINT SELECT will remain

 

 

 

 

 

 

 

 

when DISCR VS KEY SEL is OFF (0).

 

 

 

 

 

 

 

 

 

 

 

DUAL TUNING SEL

 

 

OFF, discrete parameter, 0, 1

 

 

When ON(1), selects the second set of tuning constants

 

 

 

 

 

 

 

 

(#2). A bumpless transfer (integral term adjusted)

 

 

 

 

 

 

 

 

calculation will be made on transition.

 

 

 

 

 

 

 

 

 

 

94