Honeywell VRX180 Logic Inputs, Digital Outputs AC Outputs DC Outputs, Relay Alarm Outputs

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 19
Image 19

Introduction

Table 1-1 Specifications (continued)

 

Input Impedance

51K

 

5.6K

 

 

 

Input Current

0.9 mA @ 100 Vac

 

1.1 mA @ 12 Vdc

 

 

 

 

3.2 mA @ 24 Vdc

 

Minimum ON Current

0.3 mA

 

0.3 mA

 

Maximum OFF Current

0.15 mA

 

0.2 mA

 

Base Power Required*

50 mA maximum

 

50 mA maximum

 

OFF to ON Response

5 to 30 ms

 

1 to 8 ms

 

ON to OFF Response

10 to 50 ms

 

1 to 8 ms

 

 

Logic Inputs

 

 

 

 

 

Number

6 (dry contact) per module, up to 6 modules per video recorder

 

Isolation from ground

2300 Vac/1 min.

 

 

 

 

 

Switching Voltage

5 Vdc

 

 

 

 

 

Switching Current

5 mA

 

 

 

 

 

 

Digital Outputs

 

 

 

 

 

 

AC Outputs

 

 

DC Outputs

 

Number

6 per module, up to 6 modules per video

 

6 (current sinking) per module, up to 6

 

 

recorder. Only 1-5 on each module can

 

 

modules per video recorder. Only 1-5

 

 

be configured as DAT outputs.

 

 

on each module can be configured as

 

 

 

 

 

 

DAT outputs.

 

Operating Voltage

15 to 264 Vac

 

 

10.2 to 26.4 Vdc

 

Output Type

SSR (Triac)

 

 

NPN open collector

 

Peak Voltage

264 Vac

 

 

40 Vdc

 

AC Frequency

47 to 63 Hz

 

 

N/A

 

Isolation from ground

2300 Vac/1 min.

 

 

1100 Vac/1 min.

 

Isolation between outputs

350 Vac

 

 

30 Vac

 

ON Voltage Drop

<1.5 Vac (>0.1A)

 

 

1.5 Vdc maximum

 

 

<3.0 Vac (<0.1A)

 

 

 

 

 

Maximum Load Current

0.5A per point

 

 

0.3A per point

 

Maximum Leakage Current

4 mA (264 Vac, 60 Hz)

 

 

0.1 mA @ 40 Vdc

 

 

1.2 mA (100 Vac, 60 Hz)

 

 

 

 

 

 

0.9 mA (100 Vac, 50 Hz)

 

 

 

 

 

Maximum Inrush Current

10A for 10 ms

 

 

1A for 10 ms

 

Minimum Load

10 mA

 

 

0.5 mA

 

Base Power required*

20 mA/ ON pt. 250 mA

 

 

120 mA maximum

 

 

maximum

 

 

5V

 

OFF to ON Response

1 ms

 

 

1 ms

 

ON to OFF Response

1 ms +1/2 cycle

 

 

1 ms

 

Fuses (European type 5 x

1 per output, 1.0A slow blow

 

 

1 per output

 

20mm)

 

 

 

 

1A fast blow

 

 

Relay (Alarm) Outputs

 

 

 

 

 

Number

6 per module, up to 6 modules per video recorder. Only 1-5 on each module can be

 

 

configured as DAT outputs.

 

 

 

 

 

Contact Rating

2A, 250 Vac on resistive load

 

 

 

 

 

Isolation from ground

2300 Vac/1 min.

 

 

 

 

 

Isolation between outputs

2300 Vac/1 min.

 

 

 

 

 

Contact Type

SPST normally open (NO), individually configurable to normally closed (NC) via

 

 

jumper

 

 

 

 

* Base Power Required is the power required to provided module operation within specifications.

Video Recorder - User Manual

5

Page 19
Image 19
Honeywell VRX180 user manual Logic Inputs, Digital Outputs AC Outputs DC Outputs, Relay Alarm Outputs