Programming Function Blocks and Features

CEMS Block Average

Outputs a block mean average CVn OV over the specified Average Period. The average is calculated from input samples taken at equally spaced Sample Periods. All samples are discarded at the end of the Average Period and the Average Period begins again.

Samples are ignored when Calibrate Hold is ON(1). After the Average Period the new average is calculated using only the samples taken before and after the Hold. If no valid samples are taken, the output maintains its previous value.

Table 4-48 describes the CEMS Block Average prompts. See Table 4-2 for additional prompts.

Table 4-48 CEMS Block Average Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

OFF or number

 

 

Enter the output’s display limits. Output is not clamped or

 

 

 

 

 

 

 

 

flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

OFF, analog parameter, number

 

Input to be averaged

 

 

 

 

 

 

 

 

 

 

RESET

 

OFF, discrete parameter, 0, 1

 

 

When discrete is ON(1), average is reset to zero; when

 

 

 

 

 

 

 

 

ON(1)-to-OFF(0), average restarts.

 

 

 

 

 

 

 

 

 

 

TIME UNITS

 

SECONDS, MINUTES, HOURS,

 

 

Time units of the averaging period

 

 

 

 

 

or DAYS.

 

 

 

 

 

 

 

 

 

 

 

 

 

AVERAGE PERIOD

 

OFF or number

 

 

Number of time units per average period.

 

 

 

 

 

 

 

 

 

 

SAMPLE PERIOD

 

OFF or number

 

 

Number of time units between samples. Must divide

 

 

 

 

 

 

 

 

evenly into Average Period.

 

 

 

 

 

 

 

 

 

 

CALIBRATE HOLD

 

OFF, discrete parameter, 0, 1

 

 

When ON(1), no samples are taken and the output is held.

 

 

 

 

 

 

 

 

 

 

CEMS Rolling Average (CEM Rolling Avg)

Outputs a rolling mean average CVn OV over the specified Average Period. Average is updated every Frame Period thereafter. Samples are taken at every scan cycle of the instrument, except when Calibrate Hold is ON(1).

Inp ut

 

 

 

Time

between samples

= 1 machine scan

cycle

Frame

Period

 

 

 

Average Period

 

 

 

First average

 

 

 

 

Second average

 

 

 

 

Third average

Figure 4-15 CEMS Rolling Average

Table 4-49 describes the CEMS Rolling Average prompts. See Table 4-2 for additional prompts.