Honeywell VRX180 user manual Counter Prompts, Preset, Count Down

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 127
Image 127

Programming Function Blocks and Features

Counter

Counts the number of OFF(0)-to-ON(1) transitions of the input. This number is output as CVn OV. When this number reaches the Preset value, a discrete output parameter CVn OS goes ON(1) until Reset occurs.

Table 4-21 describes the Counter prompts. See Table 4-2 for additional prompts.

Table 4-21 Counter Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output's trend display limits. Output is not clamped

 

 

 

 

 

 

 

 

or flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, discrete parameter, 0,

 

 

Input source.

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete parameter, 0,

 

 

When Reset is level high, output state (OS) is ON and the

 

 

 

 

1

 

 

counter resets to zero if counting up or to the Preset value if

 

 

 

 

 

 

 

 

counting down from it. When Reset is level low, counter

 

 

 

 

 

 

 

 

resumes counting.

 

 

 

 

 

 

 

 

 

 

 

PRESET

 

 

OFF, analog parameter,

 

 

The number of input transitions after which the CVn OS

 

 

 

 

 

number

 

 

output will go ON(1). To count forever, set to OFF. If OFF,

 

 

 

 

 

 

 

 

CVn OS will not be triggered.

 

 

 

 

 

 

 

 

 

 

 

COUNT DOWN

 

 

YES or NO

 

 

Select NO to count up from zero to the Preset value; YES to

 

 

 

 

 

 

 

 

count down from the Preset value to zero. If Preset is OFF,

 

 

 

 

 

 

 

 

Count Down must be NO.

 

 

 

 

 

 

 

 

 

 