Programming Function Blocks and Features

Logic

The input or inputs are processed by a logic operator. Call the result of this logic operation “Result”. Result is a pulse that goes ON(1) when the logic is true, and OFF(0) when the logic is not true. Result is then processed according to the specified condition type and condition time. The final output is a discrete pulse CVn OS. See Figure 4-5.

Inputs

 

 

 

 

A

 

 

 

 

B

 

 

CONDITION

 

C

 

 

 

LOGIC

 

TYPE

 

D

Result

CVn OS

 

&

E

 

 

 

OPERATOR

 

CONDITION

 

F

 

 

TIME

 

G

 

 

 

 

H

 

 

 

 

Figure 4-5 Logic Signal Flow

Table 4-25 describes the Logic prompts. See Table 4-2 for additional prompts.

Table 4-25 Logic Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

OPERATOR

 

 

AND, OR, XOR, RESET/SET FF,

 

 

See Table 4-26.

 

 

 

 

 

TOGGLE/FF, ONE SHOT, PASS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT A

 

 

OFF, discrete parameter, 0, 1.

 

 

Program at least 2 inputs. Only inputs

 

 

 

 

 

 

 

 

programmed with parameter, 1, or 0 are processed

 

 

 

 

 

 

 

 

with the operator.

 

 

INPUT B

 

 

 

 

 

 

 

 

INPUT C

 

 

 

 

 

 

 

 

INPUT D

 

 

 

 

 

 

 

 

INPUT E

 

 

 

 

 

 

 

 

INPUT F

 

 

 

 

 

 

 

 

INPUT G

 

 

 

 

 

 

 

 

INPUT H

 

 

 

 

 

 

 

 

CONDITION TYPE

 

 

NONE, DELAY, EXTEND, PULSE,

 

 

See Table 4-20 on page 111.

 

 

 

 

 

RT PULSE

 

 

 

 

 

CONDITION TIME

 

 

OFF or number

 

 

Enter number of seconds of condition time. See

 

 

 

 

 

 

 

 

Table 4-20 on page 111.

 