Programming Function Blocks and Features

Rolling Average

Outputs a rolling mean average CVn OV of the input over the specified Average Period. As new input samples are collected, old samples are discarded. The function will calculate a new average at equally spaced sample intervals.

Sample interval = averaging period

# of samples

Rolling Average = sum of samples

# of samples

Example

# of samples = 10

Average Period = 30 minutes

The first average will appear after 30 minutes, then will be updated every 30/10 or 3 minutes after.

When the Reset Input is ON(1) all accumulated samples are discarded and the output is held until the Reset Input is OFF(0), then the averaging period resets.

Table 4-46 describes the Rolling Average prompts. See Table 4-2 for additional prompts.

Table 4-46 Rolling Average Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output’s display limits. Output is not clamped or

 

 

 

 

 

 

 

 

flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog parameter,

 

 

This parameter will be averaged.

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete parameter, 0, 1

 

 

Resets average.

 

 

 

 

 

 

 

 

 

 

# OF SAMPLES

 

1-60

 

 

Number of samples taken during average period.

 

 

 

 

 

 

 

 

 

 

 

AVG PERIOD MINS

 

 

OFF or number

 

 

Number of minutes in average period.

 

 

 

 

 

 

 

 

 

 