Programming Function Blocks and Features

Table 4-6 Standard Algorithm Prompts (continued)

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

TEMPERATURE UNIT

 

 

Select C for Degrees Celsius, F for

 

 

Specifies the temperature units used for

 

 

 

 

 

Degrees Fahrenheit, K for Kelvin, R for

 

 

thermocouple, pyrometer, and RTD input

 

 

 

 

 

Rankine, or NONE.

 

 

types. The default setting is F. If you change

 

 

 

 

 

 

 

 

the default, be sure to change the analog

 

 

 

 

 

 

 

 

input’s RANGE LOW and RANGE HIGH

 

 

 

 

 

 

 

 

values accordingly. The instrument will not

 

 

 

 

 

 

 

 

adjust these values by itself.

 

 

 

 

 

 

 

 

Ignore the TEMPERATURE UNIT prompt or

 

 

 

 

 

 

 

 

set it to NONE, if the analog input being

 

 

 

 

 

 

 

 

programmed will not be used for temperature

 

 

 

 

 

 

 

 

measurements.

 

 

DIRECT/INDIRECT

 

Select DIRECT for thermocouple,

 

 

Note that the term “direct” generally applies to

 

 

 

 

 

pyrometer, or RTD inputs. Select INDIR

 

 

input types where the sensors in direct

 

 

 

 

 

(Indirect) for volt or millivolt signal inputs

 

 

physical contact with the monitored process

 

 

 

 

 

from linear or non-linear transmitters.

 

 

are also in direct physical contact with the

 

 

 

 

 

Select SQRT (Square Root) for extracting

 

 

instrument terminal board. The term “indirect”

 

 

 

 

 

flow measurements from a voltage input

 

 

applies to inputs from transmitters since the

 

 

 

 

 

representing differential pressure

 

 

sensors in direct physical contact with the

 

 

 

 

 

measurements. If SQRT is chosen, the

 

 

monitored process are indirectly connected to

 

 

 

 

 

RANGE LOW and RANGE HIGH must be

 

 

the instrument through the transmitter circuitry

 

 

 

 

 

adjusted to specify the upper and lower

 

 

and wiring.

 

 

 

 

 

limits of the flow units span.

 

 

 

 

 

CIRCUIT LOW

 

OFF or number

 

Appears only if “INDIR” or “SQRT” was

 

 

 

 

 

 

 

 

previously selected. Is the actual low end

 

 

 

 

 

 

 

 

value of voltage to be used for Indirect

 

 

 

 

 

 

 

 

measurements.

 

 

CIRCUIT HIGH

 

OFF or number

 

Appears only if “INDIR” or “SQRT” was

 

 

 

 

 

 

 

 

previously selected. Is the actual high end

 

 

 

 

 

 

 

 

value of voltage to be used for Indirect

 

 

 

 

 

 

 

 

measurements.

 

 

ELECTRICAL UNITS

 

Select whether the CIRCUIT LOW or

 

 

Circuit low and circuit high units.

 

 

 

 

 

CIRCUIT HIGH values specified are in

 

 

 

 

 

 

 

 

units of VOLTS, MV (millivolts), or OHMS.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LAG

 

 

0 seconds or OFF

 

 

“LAG” is a time constant applied to the input

 

 

 

 

 

 

 

 

measurement value. This provides digital

 

 

 

 

 

 

 

 

filtering (LAG) to the measurement.

 

 

 

 

 

 

 

 

Lag appears on menu only if EXPANDED

 

 

 

 

 

 

 

 

INPUT is enabled under Enable Features in

 

 

 

 

 

 

 

 

the Program menu.

 

 

 

 

 

 

 

 

 

SAMPLE HOLD

 

OFF, discrete parameter, 0, 1

 

Holds Input. The input value is measured

 

 

 

 

 

 

 

 

normally when this discrete is OFF and holds

 

 

 

 

 

 

 

 

its last value when the discrete is ON(1).

 

 

 

 

 

 

 

 

Hold appears on menu only if EXPANDED

 

 

 

 

 

 

 

 

INPUT is enabled under Enable Features in

 

 

 

 

 

 

 

 

the Program menu.

 

 

 

 

 

 

 

 

 

 

FAILSAFE

 

For thermocouples only, Upscale (UP),

 

 

Determines whether or not failsafe is active

 

 

 

 

 

Downscale (DOWN) or None.

 

 

and, if so, which direction.

 

 

CLAMPING

 

HI RANGE clamps the input at the

 

 

Clamps input at specified value.

 

 

 

 

 

RANGE HIGH value. LO RANGE clamps

 

 

 

 

 

 

 

 

input at the RANGE LOW value. RANGE

 

 

ATTENTION: Clamping is not recommended

 

 

 

 

 

clamps input over both the low and high

 

 

for process variable inputs to control loops.

 

 

 

 

 

range values. NONE gives no clamping.

 

 

 

 

88