Programming Function Blocks and Features

Carbon Potential

The Carbon Potential Control Function Block provides for weight percent (wt%) control of carbon in carburizing, hardening, and atmosphere generating applications.

Table 4-38 Carbon Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

PROBE TYPE

 

 

NONE, AACP, SUPER

 

 

Selection which represents the manufacturer of the

 

 

 

 

 

SYS, MARATHON, FCC

 

 

oxygen probe being used. This determines which

 

 

 

 

 

 

 

 

linearization equations are used for %C and dewpoint

 

 

 

 

 

 

 

 

calculations.

 

 

 

 

 

 

 

 

 

 

 

CARBON PROBE IN

 

 

NUMBER, PARM, OFF

 

 

Analog input that is connected to the oxygen probe mV

 

 

 

 

 

 

 

 

output.

 

 

 

 

 

 

 

 

 

 

 

PROBE TEMP INPUT

 

 

NUMBER, PARM, OFF

 

 

Analog input that is connected to the oxygen probe

 

 

 

 

 

 

 

 

temperature output.

 

 

 

 

 

 

 

 

 

 

 

TEMPERATURE UNIT

 

 

NONE, F, C, K, R

 

 

Temperature scale for this block. This selection must

 

 

 

 

 

 

 

 

match the temperature scale of the analog input that is

 

 

 

 

 

 

 

 

connected to the oxygen probe temperature output.

 

 

 

 

 

 

 

 

 

 

 

TEMP LOW LIMIT

 

 

NUMBER, OFF

 

 

Probe temperature value below which this block’s low

 

 

 

 

 

 

 

 

temperature discrete output (OS) is turned ON. This limit

 

 

 

 

 

 

 

 

and subsequent discrete output may be used to force the

 

 

 

 

 

 

 

 

control loop’s output to a known value when the probe

 

 

 

 

 

 

 

 

temperature is too low for carbon potential control.

 

 

 

 

 

 

 

 

 

 

 

CO COMPENSATION

 

 

NUMBER, PARM, OFF

 

 

Number used in the %C calculation which represents the

 

 

 

 

 

 

 

 

%CO present in the endothermic gas.

 

 

 

 

 

 

 

 

 

 

 

FURNACE FACTOR

 

 

NUMBER, PARM, OFF

 

 

Correction factor used to account for environmental

 

 

 

 

 

 

 

 

variation within the furnace chamber. In units of %C, this

 

 

 

 

 

 

 

 

factor is added directly to the %C value calculated from

 

 

 

 

 

 

 

 

probe output linearization.

 

 

 

 

 

 

 

 

 

 

 

SOOTING FACTOR

 

 

ON, OFF

 

 

Boolean value that determines whether the anti-sooting

 

 

 

 

 

 

 

 

factor output (A1) will be based linearly on probe

 

 

 

 

 

 

 

 

temperature (SOOTING FACTOR=ON) or a constant

 

 

 

 

 

 

 

 

value of 2.0 (SOOTING FACTOR=OFF). If SOOTING

 

 

 

 

 

 

 

 

FACTOR is ON, a probe temperature of 1408 ° F or

 

 

 

 

 

 

 

 

below limits %C output to 0.75% and 2086 ° F or above

 

 

 

 

 

 

 

 

limits %C output to 2.0%.

 

 

 

 

 

 

 

 

 

 

 

PERCENTAGE

 

 

NUMBER, OFF

 

 

Number representing %H2 that is used in the dewpoint

 

 

HYDROGEN

 

 

 

 

 

calculation.

 

 

 

 

 

 

 

 

 

 