Programming Function Blocks and Features

Interval Timer

This timer counts down from the preset value in minutes. This time remaining is CVn OV. The timer has a single discrete output CVn OS which is ON(1) while the timer is actively counting or while RESET is ON(1), and OFF(0) while the timer has timed out to zero. When RESET/RUN switches ON(1) the timer resets to the preset value; an ON(1) to OFF(0) transition starts the timer.

Table 4-34 describes the Interval Timer prompts. See Table 4-2 for additional prompts.

Table 4-34 Interval Timer Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

PRESET

 

 

OFF, analog parameter,

 

 

Timer counts to zero from this number of minutes.

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET/RUN

 

 

OFF, discrete parameter, 0, 1

 

 

Controls the operation of the timer.

 

 

 

 

 

 

 

 

 

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output’s display limits. Output is not clamped or

 

 

 

 

 

 

 

 

flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 