Programming Function Blocks and Features

Table 4-41 Advanced Splitter Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RANGE LOW

 

 

OFF or number

 

 

Enter the output's display limits. Output is not clamped or

 

 

 

 

 

 

 

 

flashed when it exceeds these limits.

 

 

RANGE HIGH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog parameter,

 

 

Input source. Typically, this is the output value (OV) of a

 

 

 

 

 

number

 

 

Split Output type of loop.

 

 

 

 

 

 

 

 

 

 

 

FEEDBACK #1

 

 

OFF, AOn BC, LPn BC

 

 

Select the back calculation value (BC) of the analog output

 

 

 

 

 

 

 

 

assigned to the A1, A2, and A3 outputs, respectively.

 

 

 

 

 

 

 

 

 

 

 

FEEDBACK #2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FEEDBACK #3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT#1 IN LO LIM

 

 

OFF or number

 

Enter a range for A1's input. Defauts are 0 for low limit & 30

 

 

 

 

 

 

 

 

for high limit. When input is between these values, A1

 

 

OUT#1 IN HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

output is scaled between OUT#1 OUT LO LIM & OUT#2

 

 

 

 

 

 

 

 

OUT HI LIM.

 

 

 

 

 

 

 

 

 

 

OUT#1 OUT LO LIM

 

 

OFF or number

 

Enter OFF or a range for A1’s output. Defaults are 0 for low

 

 

 

 

 

 

 

 

limit & 100 for high limit. Scales A1 output.

 

 

OUT#1 OUT HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT#2 IN LO LIM

 

 

OFF or number

 

Enter a range for A2’s input. Defaults are 30 for low limit &

 

 

 

 

 

 

 

 

60 for high limit. When input is between these values, A2

 

 

OUT#2 IN HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

output is scaled between OUT#2 OUT LO LIM & OUT#2

 

 

 

 

 

 

 

 

OUT HI LIM.

 

 

 

 

 

 

 

 

 

 

OUT#2 OUT LO LIM

 

 

OFF or number

 

Enter OFF or a range for A2’s output. Defaults are 0 for low

 

 

 

 

 

 

 

 

limit & 100 for high limit. Scales A2 output.

 

 

OUT#2 OUT HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUT#3 IN LO LIM

 

 

OFF or number

 

Enter a range for A3’s input. Defaults are 60 for low limit &

 

 

 

 

 

 

 

 

90 for high limit. When input is between these values, A3

 

 

OUT#3 IN HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

output is scaled between OUT#3 OUT LO LIM & OUT#3

 

 

 

 

 

 

 

 

OUT HI LIM.

 

 

 

 

 

 

 

 

 

 

OUT#3 OUT LO LIM

 

 

OFF or number

 

Enter OFF or a range for A3’s output. Defaults are 0 for low

 

 

 

 

 

 

 

 

limit & 100 for high limit. Scales A3 output.

 

 

OUT#3 OUT HI LIM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

134