Honeywell VRX180 user manual Program Alarms, Alarm Prompts

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 157
Image 157

Programming Function Blocks and Features

4.13 Program Alarms

You can program an alarm to be triggered by any extreme input value. To program alarms, select “PROGRAM ALARMS” on the Main Program Menu. Select an alarm to program.

REFERENCE

When an alarm occurs, it produces an output pulse which can be configured to trigger a discrete output (such as a relay). Refer to Section 4.11 for instructions.

Table 4-50 describes the Alarm prompts. See Table 4-2 for additional prompts.

Table 4-50 Alarm Prompts

 

Prompt

 

 

Range/Selections

 

 

 

Definition

 

 

ON STATE

 

 

See Table 4-3 for

 

 

Enter labels for on and off states of alarm

 

 

 

 

 

choices.

 

 

 

 

 

 

OFF STATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALARM ACTION

 

HIGH

 

 

Alarm when input value

set point value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW

 

 

Alarm when input value

set point value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEV

 

 

Deviation. Alarm when input value deviates above or below compare

 

 

 

 

 

 

 

 

point value by an amount set point value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HDEV

 

 

High deviation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LDEV

 

 

Low deviation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HRATE

 

 

High Rate. Alarm when input value increases at rate set point

 

 

 

 

 

 

 

 

value, in units per minute. Negative rate set points are processed as

 

 

 

 

 

 

 

 

positive values. May take up to 30 seconds to activate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LRATE

 

 

Low Rate. Alarm when input value decreases at rate set point

 

 

 

 

 

 

 

 

value, in units per minute. Negative rate set points are processed as

 

 

 

 

 

 

 

 

positive values. May take up to 30 seconds to activate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

 

 

No alarm action.

 

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog

 

 

Input source monitored by alarm.

 

 

 

 

 

parameter, number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETPOINT

 

 

OFF, analog

 

 

Point at which alarm occurs.

 

 

 

 

 

parameter, number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COMPARE

 

 

OFF, analog

 

 

DEV type only. It is the point against which the input point is

 

 

POINT

 

 

parameter, number

 

 

compared. The difference between the input point and the compare

 

 

 

 

 

 

 

 

point is the value which is measured against the alarm set point.

 

 

 

 

 

 

 

 

 

 

 

HYSTERESIS

 

 

OFF or number

 

 

Hysteresis affects only the point at which an alarm clears. A high

 

 

 

 

 

 

 

 

alarm will clear when the input is less than the set point minus the

 

 

 

 

 

 

 

 

hysteresis value. A low alarm will clear when the input is greater than

 

 

 

 

 

 

 

 

the set point plus the hysteresis value. A deviation alarm will clear

 

 

 

 

 

 

 

 

when the input is less than the set point minus the hysteresis value.

 

 

 

 

 

 

 

 

 

 

 

DELAY TIME

 

 

OFF or number

 

 

If the alarm condition clears before the delay time (in seconds)

 

 

 

 

 

 

 

 

expires, no alarm will be indicated. Delay time must be in multiples of

 

 

 

 

 

 

 

 

scan time.

 

 

 

 

 

 

 

 

 

 

 

 

SAMPLE HOLD

 

 

OFF, discrete

 

 

When this parameter level = 1, the alarm processing is disable and

 

 

 

 

 

parameter, 0 or 1

 

 

the output is held.

 

 

 

 

 

 

 

 

 

 

 

 

Video Recorder – User Manual

143

Page 157
Image 157
Honeywell VRX180 user manual Program Alarms, Alarm Prompts