Setpoint Profiler

Table 5-2 Parameters That Control Profiler Execution (continued)

Parameter name

 

 

 

Definition

 

 

 

Triggered

 

 

Conditions

 

 

Result

 

 

 

 

 

 

 

 

 

 

by

 

 

present

 

 

 

 

 

HOLD

 

 

Holds a profiler at its current position.

 

 

Level ON

 

Profiler is in

 

 

Profiler is

 

 

 

 

 

Profiler’s Elapsed Time continues but

 

 

 

 

 

Run or Hold

 

 

put in Hold

 

 

 

 

 

Segment Time stops until Profiler is started

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

again.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hold is activated by online operator menu or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

by a discrete input. May be connected to F2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

key (SY1F2).

 

 

 

 

 

 

 

 

 

 

 

ADVANCE

 

 

Advances a profiler on Hold to the starting

 

 

Rising

 

 

Profiler is in

 

 

Profiler

 

 

 

 

 

value of the next segment. If the profile is on

 

 

edge

 

 

Hold

 

 

advances

 

 

 

 

 

the last segment, it advances to the ending

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value of the last segment. If the profile is on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the ending value of the last segment of the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

batch, then it advances around to the starting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value of segment 1, or to the first segment of

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the batch phase as defined by BATCH

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SEGMENT FIRST. If within a loop, advances

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

to next segment in the loop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Advance is activated by online operator menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

or by a discrete input.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOT START

 

 

When HOT START is ON and the profiler is

 

 

Level ON

 

Profiler is in

 

 

When

 

 

 

 

 

started, the profiler begins to run at the point

 

 

 

 

 

Ready

 

 

profiler

 

 

 

 

 

in the profile where the current value of PV #1

 

 

 

 

 

 

 

 

changes

 

 

 

 

 

first occurs. Hot Start makes the profiler skip

 

 

 

 

 

 

 

 

from Ready

 

 

 

 

 

over unneeded segments.

 

 

 

 

 

 

 

 

to Run,

 

 

 

 

 

Hot Start is activated by a discrete input.

 

 

 

 

 

 

 

 

profiler

 

 

 

 

 

 

 

 

 

 

 

 

 

jumps to

 

 

 

 

 

Example

 

 

 

 

 

 

 

 

the same

 

 

 

 

 

 

 

 

 

 

 

 

 

value as

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If PV #1 is 100 and the profile contains the

 

 

 

 

 

 

 

 

PV #1

 

 

 

 

 

value 100 in Segment 4 and Segment 6, HOT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START forces the profiler to start running at

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Segment 4 at 100, not at Segment 1 or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Segment 6.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Figure 5-10 Hot Start.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV#1

If Hot Start = ON, Profile starts at first intersecting point between profile and PV #1.

Profile starts here

Figure 5-10 Hot Start