Programming Function Blocks and Features

Table 4-10 Loop Prompts (continued)

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

IN DECIMAL

 

 

Select decimal position

 

Used for all input parameters of the loop.

 

 

POSITION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTERACTIVE

 

 

YES, NO

 

 

Select interactive (YES) or noninteractive (NO) for the control

 

 

 

 

 

 

 

 

algorithm operation. Interactive causes the Gain, Rate, and

 

 

 

 

 

 

 

 

Reset terms to interact to make up the proportional term of

 

 

 

 

 

 

 

 

the algorithm (similar to analog controllers). In noninteractive

 

 

 

 

 

 

 

 

the proportional term is simply related to Gain.

 

 

 

 

 

 

 

 

 

 

 

LATCHING

 

 

YES, NO

 

 

Select the desired action required after a failure to the

 

 

 

 

 

 

 

 

failsafe status.

 

 

 

 

 

 

 

 

When the loop’s PV or Set point #2 fails, the downstream

 

 

 

 

 

 

 

 

function block activates its failsafe (See Table 9-3, Default

 

 

 

 

 

 

 

 

condition column). If latching = YES, when the failure is

 

 

 

 

 

 

 

 

corrected the operator must take specific action to cancel

 

 

 

 

 

 

 

 

these failsafe measures and return the loop to normal

 

 

 

 

 

 

 

 

operation. (See Table 9-3 for action needed.) If latching =

 

 

 

 

 

 

 

 

NO, when the failure is corrected the loop will automatically

 

 

 

 

 

 

 

 

return to normal operation with no action needed by the

 

 

 

 

 

 

 

 

operator.

 

 

 

 

 

 

 

 

 

 

 

MANUAL OFF

 

 

OFF, discrete parameter, 0,

 

 

When this discrete input goes ON (1) it causes the control

 

 

 

 

1

 

 

output to go off.

 

 

 

 

 

 

 

 

 

 

 

MANUAL RESET

 

 

-100 to +100

 

 

This feature functions only when OFF is entered for RESET.

 

 

 

 

 

 

 

 

Enter a value equal to the desired loop output when the

 

 

 

 

 

 

 

 

process variable is at set point. This allows correction of

 

 

 

 

 

 

 

 

output to account for load changes to bring the process

 

 

 

 

 

 

 

 

variable up to set point.

 

 

 

 

 

 

 

 

 

 

OUTPUT LOW LIM &

 

 

OFF or number

 

For cascade primary loop, set to PV LOW LIMIT and PV

 

 

OUTPUT HIGH LIM

 

 

 

 

 

HIGH LIMIT of the cascade secondary loop, respectively.

 

 

 

 

 

 

 

 

 

 

 

OUTPUT TRACKING

 

 

0-100%, Analog parameter,

 

 

This will be the loop's output value when the FORCE

 

 

 

 

 

OFF

 

 

REMOTE MAN input to the loop is high (1). See Force

 

 

 

 

 

 

 

 

Remote Man.

 

 

 

 

 

 

 

 

 

 

 

PROCESS

 

 

OFF, analog parameter,

 

 

Process variable for the loop.

 

 

VARIABLE

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROP BAND#1 &

 

 

 

 

 

See GAIN#1 OR GAIN#2

 

 

PROP BAND#2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PV LOW LIMIT &

 

 

OFF or number

 

 

Enter the high and low limits for the process variable being

 

 

PV HIGH LIMIT

 

 

 

 

 

controlled. Loop tuning parameters are based on the span

 

 

 

 

 

 

 

 

selected by the high and low limit values.

 

 

 

 

 

 

 

 

 

 

 

PV TRACKING

 

 

PV, OFF

 

 

A selection of Process Variable (PV) will cause Set point #1

 

 

 

 

 

 

 

 

of the control loop to track the process variable when the

 

 

 

 

 

 

 

 

loop is in Manual mode. A transfer to Automatic mode will

 

 

 

 

 

 

 

 

maintain the tracked set point value as the working set point

 

 

 

 

 

 

 

 

of the loop unless the loop was operating from Set point 2

 

 

 

 

 

 

 

 

prior to the transfer to Manual.

 

 

 

 

 

 

 

 

 

 