Programming Function Blocks and Features

Signal Clamp

If input is between Low Select and High Select, the output CVn OV equals the input. If the input exceeds these two limits, the output equals the preset value.

Table 4-44 describes the Signal Clamp prompts. See Table 4-2 for additional prompts.

Table 4-44 Signal Clamp Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

OUT LOW LIMIT

 

 

OFF or number

 

 

Displayed output value will be clamped and will flash

 

 

 

 

 

 

 

 

when these limits are exceeded.

 

 

OUT HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOW SELECT

 

 

OFF, analog parameter,

 

 

If input goes below this number, the output will equal the

 

 

 

 

 

number

 

 

preset value. Otherwise, the output equals the input.

 

 

 

 

 

 

 

 

 

 

 

HIGH SELECT

 

 

OFF, analog parameter,

 

 

If input goes above this number, the output will equal the

 

 

 

 

 

number.

 

 

preset value. Otherwise, the output equals the input.

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, analog parameter,

 

 

Input to be clamped.

 

 

 

 

 

number

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESET

 

 

OFF, analog parameter,

 

 

Output will go to this value when the input exceeds the

 

 

 

 

 

number.

 

 

low or high select values.

 

 

 

 

 

 

 

 

 

 