Programming Function Blocks and Features

4.24 Scan Rate

Scan rate is the time required to measure inputs, execute function blocks (AI, Loops, AO, DI, DO, CV, etc.) and update outputs. It is also known as the machine cycle, scan cycle, and update rate.

The Scan Rate prompt lets you set the scan rate of the instrument to a value slower than the maximum rate allowed by the hardware. The hardware will determine the default scan rate. Allowable entries are 250 milliseconds, 500 milliseconds, 1 second, 2 or 3 seconds. 250 ms rate is only available on 4 input units.

We recommend the following scan rates for the following configurations.

Table 4-70 Suggested Scan Rates

 

Inputs

 

 

Scan Rate

 

 

W/Control

 

 

Up to 4

 

 

250 msec

 

 

500 msec

 

 

Up to 12

 

 

500 msec

 

 

1 sec

 

 

Up to 16

 

 

750 msec

 

 

1 sec

 

 

Up to 24

 

 

1 sec

 

 

1.5 sec

 

 

Up to 32

 

 

1.5 sec

 

 

2 sec

 

 

Up to 44

 

 

2.0 sec

 

 

2 sec

 

 

Up to 48

 

 

3.0 sec

 

 

3 sec

 

 

 

 

 

 

 

 

 

 

NOTE

These are suggested scan rates. In general, if your instrument responds too slowly, use a slower (higher) scan rate. You can use a faster (lower) scan rate than suggested here, but be aware of possible sluggish display and button response time.