Programming Function Blocks and Features

4.11 Program Discrete Outputs

Discrete Output function blocks control the relay or open collector output hardware. The Program Discrete Outputs menu item will appear if a Discrete Outputs board is installed.

ATTENTION

If a discrete output has been assigned to a time proportioning output (DAT), it will not be programmable here. See "OUTPUT RELAY" in Table 4-13.

Select a DO to program, then program the prompts in Table 4-15. See Table 4-2 for additional prompts.

Table 4-15 Discrete Output Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

ACTION STATE

 

 

NORMAL, INVERT

 

 

Determines whether the relay will normally be energized or

 

 

 

 

 

 

 

 

de-energized when the DO’s Input is ON(1). To select

 

 

 

 

 

 

 

 

energized when ON, enter NORMAL (not inverted). To select

 

 

 

 

 

 

 

 

energized when OFF, enter INVERT (inverted).

 

 

 

 

 

 

 

 

 

 

 

INPUT

 

 

OFF, discrete parameter, 0,

 

 

Source of the Discrete Output.

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EVENT ENABLE

 

 

NONE, RISING, FALLING,

 

 

Determines whether changes in DO’s status can be recorded

 

 

 

 

 

BOTH

 

 

as events in data storage. For storage to occur, Data

 

 

 

 

 

 

 

 

Storage must also be programmed to store Events.

 

 

 

 

 

 

 

 

NONE - status changes are not stored

 

 

 

 

 

 

 

 

RISING - OFF(0)-to-ON(1) changes can be stored

 

 

 

 

 

 

 

 

FALLING - ON(1)-to-OFF(0) changes can be stored

 

 

 

 

 

 

 

 

BOTH - Rising and falling changes can be stored

 

 

 

 

 

 

 

 

 

 