Honeywell VRX180 user manual Edit Profile Prompts

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 207
Image 207

 

 

 

 

Setpoint Profiler

 

 

Table 5-5 Edit Profile Prompts

 

 

 

 

 

 

Prompt

 

Range/Selections

 

Definition

 

RAMP TYPE

 

VAL/DUR, TIME, RATE,

 

See 4 types of ramp segments on page 178.

 

 

EXTERNAL

 

 

 

 

 

 

 

 

TIME UNITS

 

SECS, MINS, HOURS

 

Select the time units to be used by all segments

 

 

 

 

of the profile.

 

 

 

 

 

EDIT SEGMENTS

 

 

 

See Table 5-6.

 

 

 

 

 

GUAR SOAK LO LIM

 

OFF or number

 

The profiler will Hold if PV #1 or PV #2 deviates

 

 

 

 

more than this much below the profiler output.

 

 

 

 

See Guaranteed Soak on page 182 for details.

 

 

 

 

 

GUAR SOAK HI LIM

 

OFF or number

 

The profiler will Hold if PV #1 or PV #2 deviates

 

 

 

 

more than this much above the profiler output.

 

 

 

 

See Guaranteed Soak on page 182 for details.

 

 

 

 

 

HYSTERESIS

 

OFF or number

 

See Hysteresis on page 182 for details.

 

 

 

 

 

BATCH FIRST

 

0-63

 

Specify the first segment of the batch phase.

SEGMENT

 

 

 

Prior segments are the start-up phase. A value

 

 

 

 

of 0 indicates a single phase profile. See Two

 

 

 

 

types of profiles on page 177 for details.

 

 

 

 

 

BATCH LAST

 

0-63

 

Specify the last segment of the batch phase.

SEGMENT

 

 

 

Segments after this segment are the shutdown

 

 

 

 

phase. A value of 0 indicates a single phase

 

 

 

 

profile. See Two types of profiles on page 177

 

 

 

 

for details.

 

 

 

 

 

 

 

 

 