Online Operation Using Menus

7.6 Tune Loop

This option lets you tune (change) various loop parameters online. These tunable parameters depend on the loop type in use and are described in Section 4.8, Program Control Loops. Also, the following menu choices are available.

Table 7-9 Tune Loop Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

LOOP TYPE

 

 

STD, ADV, SPLIT, ON OFF,

 

 

STD: Standard

 

 

 

 

 

CAS P, CAS S, RATIO,

 

 

ADV: Advanced

 

 

 

 

 

DIAT

 

 

SPLIT: Split Output

 

 

 

 

 

 

 

 

ON OFF: On/Off

 

 

 

 

 

 

 

 

CAS P: Cascade Primary

 

 

 

 

 

 

 

 

CAS S: Cascade Secondary

 

 

 

 

 

 

 

 

RATIO: Ratio

 

 

 

 

 

 

 

 

DIAT: DIAT

 

 

PV

 

 

Number

 

Value of PV

 

 

 

 

 

 

 

 

 

 

 

OUTPUT

 

 

-100 to +100

 

 

Loop output %.

 

 

 

 

 

 

 

 

 

 

 

SETPOINT SOURCE

 

 

SP1 or SP2

 

 

Indicates which setpoint is being used by the loop. SP1 must

 

 

 

 

 

 

 

 

be a number; SP2 may be a number or a value from a

 

 

 

 

 

 

 

 

function block (remote setpoint).

 

 

 

 

 

 

 

 

 

Bold items are read-only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOGGLE SETPOINT

 

 

SP1, SP2

 

 

Press Enter to change the Setpoint Source from SP1 to SP2

 

 

SOURCE

 

 

 

 

 

or vice versa.

 

 

 

 

 

 

 

 

 

 

 

SETPOINT #1

 

 

Number

 

 

Enter the new value of SP1.

 

 

 

 

 

 

 

 

 

 

 

SETPOINT #2

 

 

Number or parameter

 

 

Enter the new value of SP2. If SP2 is a remote setpoint you

 

 

 

 

 

 

 

 

cannot change the value here.

 

 

 

 

 

 

 

 

 

 

 

PROP. BAND #1

 

 

 

 

 

See Gain #1.

 

 

 

 

 

 

 

 

 

 

GAIN #1

 

Enter a value of 0.1 to 200

 

 

Gain is the proportional gain entry for the control loop (The

 

 

 

 

 

for Gain, or 0.5 to 1000.0 for

 

 

value entered here is the gain applied to the error signal to

 

 

 

 

 

Proportional Band. Enter

 

 

determine the loop output. For example, a 10% change in

 

 

 

 

 

OFF to allow integral only

 

 

process variable (with respect to the input range) from a

 

 

 

 

 

control.

 

 

balanced condition will result in a 10% change in output,

 

 

 

 

 

 

 

 

when a gain of 1.0 is used. Enter a starting value at initial

 

 

 

 

 

 

 

 

configuration. The value may be altered Online for final loop

 

 

 

 

 

 

 

 

tuning. If an indirect source is specified as in an adaptive

 

 

 

 

 

 

 

 

gain configuration, the value can only be altered at the

 

 

 

 

 

(Variable Gain1 or PB1 is

 

 

source.

 

 

 

 

 

available by programming a

 

 

Gain and Proportional Band are interchangeable values

 

 

 

 

 

constant's Destination with

 

 

 

 

 

 

 

 

 

(Proportional Band = 100/Gain). For loops with dual tuning,

 

 

 

 

 

GN or PB. See Program

 

 

 

 

 

 

 

 

 

Gain 1 is the gain for the first set of tuning parameters. Gain

 

 

 

 

 

Constants, Section 4.16.)

 

 

 

 

 

 

 

 

 

2 is for the second set.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 