Programming Function Blocks and Features

4.20 Program Security

Security lets you protect certain menu items and functions from unwanted or accidental access. Access to a secured item requires entry of a 3-digit master or operator code.

Select “PROGRAM SECURITY” to display the Security menu (if security is active, you will be prompted to enter the master code before continuing).

REFERENCE

If the master or operator’s security code is lost or forgotten, a security bypass procedure is available. See Appendix A.

Table 4-66 describes the Security prompts.

Table 4-66 Security Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

ENABLE SECURITY

 

 

YES, NO

 

 

Set to Yes to activate security on all enabled security items

 

 

 

 

 

 

 

 

having a non-zero master or operator’s code. If set to No, no

 

 

 

 

 

 

 

 

items will be secure!

 

 

 

 

 

 

 

 

 

 

 

MASTER SEC CODE

 

 

3 digit number

 

 

Set to a non-zero value; a value of zero offers no security.

 

 

 

 

 

 

 

 

Secures the following items:

 

 

 

 

 

 

 

 

MEMORY CLEAR SERVICES in Maintenance mode.

 

 

 

 

 

 

 

 

PROGRAM SECURITY in Program mode

 

 

 

 

 

 

 

 

Changing out of Online Mode. (See SET MODE.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET MODE

 

 

Set to Yes to secure changing from Online mode to Program or

 

 

 

 

 

 

 

 

Maintenance modes.

 

 

 

 

 

 

 

 

 

 

OPERATOR SEC

 

 

3 digit number

 

Enter a non-zero operator security code value; a value of zero

 

 

CODE

 

 

 

 

 

offers no security. Secures the following items (if set to Yes).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AUTO/MANUAL

 

 

Set to Yes to secure Online changes between a loop’s Auto and

 

 

 

 

 

 

 

 

Manual modes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP1/SP2

 

 

Set to Yes to secure Online changes between a loop’s SP1 and

 

 

 

 

 

 

 

 

SP2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETUP PARAMETERS

 

 

Set to Yes to secure changes to:

 

 

 

 

 

 

 

 

Online Data Entry menu items:

 

 

 

 

 

 

 

 

Alarm Set points

 

 

 

 

 

 

 

 

Analog Input Adjust

 

 

 

 

 

 

 

 

Online Tune Loop menu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

REVIEW PROGRAM

 

 

Set to Yes to secure Online access to Review Programming (via

 

 

 

 

 

 

 

 

REVIEW PROGRAMMING menu).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DATA STORAGE

 

 

Set to Yes to secure access to any part of data storage (via

 

 

 

 

 

 

 

 

Online DATA STORAGE SETUP menu). Does not affect access

 

 

 

 

 

 

 

 

to Online DATA STORAGE STATUS display.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROFILER

 

 

Set to Yes to secure access to all Set point Profiler menus and

 

 

 

 

 

 

 

 

displays.

 

 

 

 

 

 

 

 

 

 

160

Video Recorder – User Manual

Page 174
Image 174
Honeywell VRX180 user manual Program Security, Security Prompts