Programming Function Blocks and Features

Display Setup Procedure

Table 4-54 describes the display setup procedure.

Table 4-54 Display Setup Procedure

Step

 

Action

 

 

 

1Select Program Displays from the Program mode menu.

2For each display format desired (trend, bar graph, panel display, unit data), specify points to be displayed.

3Assign up to 10 displays to the Display buttons.

Set Up Trend 1

Table 4-55 describes the trend display setup procedure.

Table 4-55 Set Up Trend 1 Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

ENABLE

 

 

Yes, No

 

 

Enables or disables a specific trend.

 

 

 

 

 

 

 

 

 

 

 

POINT #1

 

 

Analog or discrete

 

 

Select up to 12 analog or discrete points to be displayed as a

 

 

POINT #12

 

 

parameters

 

 

vertical or horizontal trend. Trends of discrete points will

 

 

 

 

 

 

 

 

show a value of 1 when ON and 0 when OFF.

 

 

 

 

 

 

 

 

 

 

 

NORM TIME BASE

 

 

5, 15, or 30 minutes, or 1, 2,

 

 

Enter the trend display time base for Normal (typically slow

 

 

 

 

 

4, 8, 24 hours, 7 days or

 

 

speed). The time base is the time period shown for one full

 

 

 

 

 

31 days. Equivalent paper

 

 

screen.

 

 

 

 

 

chart speeds are listed in

 

 

 

 

 

 

 

 

Table 4-56.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ALT TIME BASE

 

 

5, 15, or 30 minutes, or 1, 2,

 

 

Enter the trend display time base for Alternate (typically fast

 

 

 

 

 

4, 8, 24 hours, 7 days or 31

 

 

speed). The time base is the time period shown for one full

 

 

 

 

 

days. Equivalent paper

 

 

screen.

 

 

 

 

 

chart speeds are listed in

 

 

 

 

 

 

 

 

Table 4-56.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SET DISPLAY

 

 

OFF or number

 

 

Set the high and low full-scale display limits for each point. If

 

 

LIMITS

 

 

 

 

 

you select OFF for a limit on this display, the limits

 

 

 

 

 

 

 

 

programmed for the analog point (either RANGE LOW and

 

 

 

 

 

 

 

 

RANGE HIGH or OUT LOW LIMIT and OUT HIGH LIMIT) will

 

 

 

 

 

 

 

 

be used as the trend limits for that point.

 

 

 

 

 

 

 

 

The accuracy of a trended point is determined only by the

 

 

 

 

 

 

 

 

original output limits of the point, not by setting wider or

 

 

 

 

 

 

 

 

narrower limits here. Setting excessively narrower limits here

 

 

 

 

 

 

 

 

will result in a viewable trend with a high degree of

 

 

 

 

 

 

 

 

inaccuracy when viewed as a % of the screen. To increase

 

 

 

 

 

 

 

 

accuracy over a narrower range, decrease the programmed

 

 

 

 

 

 

 

 

output range (limits) of the point itself.

 

 

 

 

 

 

 

 

 

 

 

TIMEBASE

 

 

OFF, discrete parameter, 0,

 

 

Enter a discrete parameter which will cause trend to display

 

 

SELECTOR

 

1

 

 

alternate timebase when ON and normal timebase when

 

 

 

 

 

 

 

 

OFF.

 

 

 

 

 

 

 

 

 

 

152

Video Recorder – User Manual

Page 166
Image 166
Honeywell VRX180 user manual Display Setup Procedure, Set Up Trend 1 Prompts