Honeywell VRX180 user manual Trend Data 2, 3, Alarms, Stored Events

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 183
Image 183

Programming Function Blocks and Features

Trend Data 2, 3 & 4

Trend Data 2, Trend Data 3 and Trend Data 4 use the same prompts as in Table 4-72.

Alarms

Alarm data storage consists of a complete log of alarms, including time of occurrence, time of clearing, value of the alarm parameter, the alarm sense (high, low, etc.) and the batch identification number, if present. The alarm prompts are: STORAGE MODE, ROLLOVER, ALARM SAMPLES, EXTERNAL ENABLE, SELECT FILENAME. See Table 4-72 for descriptions.

The number of samples which can be stored in a file (ALARM SAMPLES) can be up to

1600. Depending on your selections, data collection will begin when the first alarm occurs, or when the first alarm occurs after a batch start.

Events

Event storage consists of a complete log of events including the event title, time of occurrence, the status or value after the change, and the batch identification number, if present. When event storage is running, loop and instrument mode events are always stored; discrete input and output events are stored only if first enabled under those items’ program menus (see Sections 4.10 and 4.11).

 

 

Table 4-73 Stored Events

 

 

 

 

 

 

 

 

 

Event title

 

 

 

Event status/value

 

 

Setpoint choice

 

 

SP1, SP2

 

 

Control action

 

 

Forward, Reverse

 

 

Tuning Set

 

 

Set 1, Set 2

 

 

Instrument Mode

 

 

Online, Program, Maint

 

 

Control Mode

 

 

Auto, Manual, RMan

 

 

Set point 1

 

 

 

SP1’s value

 

 

Set point 2

 

 

 

SP2’s value

 

 

Control Output

 

 

 

Loop’s output value

 

 

Discrete Input

 

 

On, Off

 

 

Discrete Output

 

 

On, Off

 

Event storage setup is done with the following parameters: STORAGE MODE, ROLLOVER, EVENT SAMPLES, EXTERNAL ENABLE, SELECT FILENAME. See Table 4-72 for parameter descriptions.

The number of samples which can be stored in a file (EVENT SAMPLES) can be up to 1600.

Depending on your selections, data collection will begin when the first event occurs, or when the first event occurs after a batch start.

Barcode data is also stored in the event file.