Diagnostic and error messages

9.2 Loop Error Indicators

When a loop's PV, SP2, or other parameter fails, the loop switches to its default/failsafe condition, indicated by certain display symbols flashing. To return the loop to its desired condition, correct the failure. Then, if the loop's LATCHING is NO, the loop will return to normal automatically. If LATCHING is YES, also perform the action needed to return the loop to normal.

Table 9-3 Abnormal Loop Conditions And Indicators

Desired Condition

 

 

 

Abnormal Condition

 

 

 

Default condition

 

 

 

Flashing

 

 

 

Action needed

 

 

 

 

 

 

 

 

 

 

(Failsafe)

 

 

 

symbols

 

 

 

(if LATCHING = YES)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto & SP2

 

 

SP2 Failure

 

 

Working SP=SP1

 

 

SP2

 

 

Select SP1 then SP2

 

 

 

 

 

 

 

 

 

 

Manual & SP2

 

SP2 Failure

 

Working SP=SP1

 

SP2

 

 

Select SP1 then SP2

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto & SP2

 

 

SP2 & PV Failure

 

 

Working SP=SP1

 

 

SP2

 

 

Select SP1 then SP2

 

 

 

 

 

 

 

 

Mode = Suspend Auto*

 

 

AUTO

 

 

Select Manual then

 

 

 

 

 

 

 

 

 

 

MAN**

 

 

Auto

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output = Failsafe

 

 

PV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual & SP2

 

SP2 & PV Failure

 

Working SP = SP1

 

 

SP2

 

 

Select SP1 then SP2

 

 

 

 

 

 

 

 

Mode = Manual

 

 

PV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output = Last value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto & SP1/SP2

 

 

PV Failure or

 

 

Mode = Suspend Auto*

 

 

AUTO

 

 

Select Manual then

 

 

 

 

Force Remote Manual

 

 

Output = Failsafe

 

 

MAN**

 

 

Auto

 

 

 

 

 

 

 

 

PV

 

 

 

 

 

 

 

 

 

Failure or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output Tracking

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure or

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Feedforward Failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Manual & SP1/SP2

 

 

PV Failure

 

 

Mode = Manual

 

 

PV

 

 

None required

 

 

 

 

 

 

 

 

Output = Last Value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto & SP1/SP2

 

See below***

 

 

Mode = Suspend Auto*

 

 

AUTO

 

 

None required

 

 

 

 

 

 

 

 

Output = Back Calc. Value

 

 

MAN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto & SP1/SP2

 

 

Force Remote Manual

 

 

Mode = Suspend Auto*

 

 

AUTO

 

 

None required

 

 

 

 

 

 

 

 

Output = Tracking value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Due to the abnormal condition the loop cannot be in Auto and therefore is in a temporary mode which forces the output as indicated.

**If loop feedback is not connected to an AO, or if loop type is ON/OFF, then MAN will be steady, not flashing.

***Status from a downstream function block indicates that there is no path to final output element. For example, the secondary control loop of cascade configuration was changed to manual mode.

254

Video Recorder – User Manual

Page 268
Image 268
Honeywell VRX180 user manual Loop Error Indicators, Abnormal Loop Conditions And Indicators