Honeywell VRX180 Program Constants, Constant Prompts, Value, Input High Limit Destination

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 161
Image 161

Programming Function Blocks and Features

4.16 Program Constants

Constants can be programmed here and their values edited Online. Select a constant to program. Table 4-52 describes the Constant prompts. See Table 4-2 for additional prompts.

Table 4-52 Constant Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

VALUE

 

 

OFF, analog

 

 

If a number, the Constant may be altered Online from the Data

 

 

 

 

 

parameter, number

 

 

Entry menu. If a parameter, this parameter can be directed by

 

 

 

 

 

 

 

 

DESTINATION to override certain programmed values.

 

 

 

 

 

 

 

 

 

 

 

INPUT LOW LIMIT

 

 

OFF or number

 

 

Display limits (for when viewing Constant on trend display or on

 

 

 

 

 

 

 

 

bar displays).

 

 

INPUT HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DESTINATION

 

 

 

 

 

See Destination defined on next page.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NONE

 

 

No destination

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn GN

 

LOOPn GAIN1

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn PB

 

LOOPn PROP. BAND #1

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn RS

 

LOOPn RESET #1

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn RA

 

LOOPn RATE #1

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn RB

 

LOOPn RATIO BIAS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn IS

 

 

LOOPn SP INC SLEW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn DS

 

LOOPn SP DEC SLEW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn HS

 

LOOPn SP HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LPn LS

 

 

LOOPn SP LOW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

AOn IS

 

AOn INC SLEW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AOn DS

 

 

AOn DEC SLEW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AOn HS

 

 

AOn IN HIGH LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

AOn LS

 

AOn IN LOW LIMIT

 

 

 

 

 

 

 

 

 

 

 

 

 

AOn IT

 

AOn IMPULSE TIME (type DAT)

 

 

 

 

 

 

 

 

 

 

COMM CONSTANT

 

 

Yes/No

 

When enabled, any constant writes via modbus communication

 

 

 

 

 

 

 

 

will only be written to the RAM copy of the configuration and not

 

 

 

 

 

 

 

 

to the non volatile flash copy.

 

 

 

 

 

 

 

 

When the unit cold starts, the constant values set up to be

 

 

 

 

 

 

 

 

periodically written via communications will revert back to any

 

 

 

 

 

 

 

 

value that was manually set via the local HMI. The local HMI will

 

 

 

 

 

 

 

 

always write the constant value to the RAM and non volatile flash

 

 

 

 

 

 

 

 

which will be preserved across a power cycle.

 

 

 

 

 

 

 

 

 

 

Video Recorder – User Manual

147

Page 161
Image 161
Honeywell VRX180 user manual Program Constants, Constant Prompts, Value, Input High Limit Destination, Comm Constant