Honeywell VRX180 How to program input parameters, Output Code Connection Procedure, Step Action

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 69
Image 69

Programming and Operating Concepts

3.11 How to program input parameters

A function block has two types of programmable parameters: input parameters and function block parameters. When in a function block’s Program menu, if a menu item has choices OFF, a number, or PARM, then the menu item is an input parameter to that function block. That is, if you choose PARM you can connect the input parameter to another function block’s output code.

How to connect an input parameter to another function block

One way to program an input parameter is to connect it to an output parameter from another function block. We will show you this procedure using a specific function block’s input parameter, but the keystrokes used in the procedure will apply when you are making any input parameter connection.

 

 

Loop

ANALOG

 

CONTROL

output

 

value

OUTPUT #1

 

LOOP #2

 

 

LP2 OV

INPUT

Number

SETPOINT#2

 

SOURCE

 

FAILSAFE

 

 

 

Figure 3-8 Example Input Parameter Connection

Assume we want to make the connections shown in Figure 3-8. We want Analog Output#1, a current output, to get its input from Control Loop#2’s output value. Therefore, we must program Analog Output#1’s Input Source parameter with the output code that represents Control Loop#2’s output value. The following procedure shows how.

 

 

 

 

Table 3-5 Output Code Connection Procedure

 

 

Step

 

 

Action

 

 

1

 

In the Program Analog Output menu, select ANALOG OUTPUT#1.

 

 

 

 

 

 

 

 

2

 

 

Consult the Program Analog Output section of this manual to learn about the menu item you wish to

 

 

 

 

 

change, namely, INPUT SOURCE.

 

 

3

 

 

Press Down Arrow button to move the cursor to the menu choice INPUT SOURCE.

 

 

4

 

 

Press Enter to move the cursor to the right side of the display where the choices for INPUT SOURCE

 

 

 

 

 

are.

 

 

5

 

 

Press Up Arrow until PARM is displayed. If you press too many times and a number is displayed,

 

 

 

 

 

continue pressing Up Arrow until PARM is displayed again. If you press Down Arrow while the

 

 

 

 

 

number is displayed, the instrument assumes you want to enter a number, not a parameter. If you

 

 

 

 

 

pressed Down Arrow, you must press Menu, then press Enter, then Up Arrow until PARM is

 

 

 

 

 

displayed.

 

 

6

 

 

Press Enter to select PARM, which gives you choices for output codes to connect to. Figure 3-9

 

 

 

 

 

shows the format for all output codes.

 

 

7

 

Press Up Arrow or Down Arrow until LP is displayed. From Table 3-4, we know LP is the designator

 

 

 

 

 

for the Control Loop function block type.

 

 

8

 

Press Enter to select LP.

 

 

9

 

Press Up Arrow or Down Arrow until 2, the Control Loop number we want, is displayed.

 

 

 

 

 

 

 

 

10

 

 

Press Enter to select 2.

 

 

 

 

 

 

 

11

 

Press Up Arrow or Down Arrow until OV is displayed. From Table 3-4 we know OV is the output

 

 

 

 

 

code for the Control Loop’s output value.

 

 

12

 

Press Enter to select OV. The cursor moves to the left and the connection from LP2 OV to Analog

 

 

 

 

 

Output#1’s INPUT SOURCE has been made.

 

Video Recorder – User Manual

55

Page 69
Image 69
Honeywell VRX180 How to program input parameters, How to connect an input parameter to another function block, Step Action