Honeywell VRX180 user manual Specifications, Physical, Environmental, Attributes

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 16
Image 16

Introduction

1.2 Specifications

 

 

Table 1-1 Specifications

 

 

 

Physical

 

 

Enclosure

Metal case and rugged die cast aluminium door and frame. High impact resistant

 

 

 

polycarbonate keypad and glass or polycarbonate window. IP55 rating (NEMA 3) from front

 

 

 

panel.

 

 

Mounting (Panel)

40 mm thickness (max.) (1,57")

 

 

Dimensions

Compact size: 320 mm (12.60") depth

 

 

 

310 mm front face height x 317 mm width (12.21" x 12.48")

 

 

 

278 mm x 278 mm (10.95" x 10.95") cutout

 

 

Weight

14 kg, depending on configuration (30 lbs)

 

 

I/O Ports Standard

PC keyboard Connector (6 pin mini DIN type) - on front panel. May be used to connect to a

 

 

 

QWERTY keyboard or to an ASCII Barcode Reader.

 

 

 

Environmental

 

 

Temperature

Operating: 5 to 40°C (41 to104°F).

 

 

 

Storage: -20 to 60°C (-4 to 158°F).

 

 

 

Relative Humidity: 10 to 90%, non-condensing at 40°C.

 

 

Altitude

< 2000 meters

 

 

Installation

II

 

 

Category

 

 

 

Pollution Degree

2

 

 

Power

Universal power supply, 100 to 240 Vac/dc, 100 VA max.

 

 

Fuse Rating

3.15 Amps, 250 Vac slow blow

 

 

 

Attributes

 

 

Display

Type: Color LCD active matrix.

 

 

 

Screen Size: 10.4" diagonal.

 

 

 

Resolution: 640 x 480 pixels.

 

 

 

Update Rate: 1 second.

 

 

 

Trend Timebase: 5 min. to 24 hrs/screen; 0.5 cm/hr to 154 cm/hr vertical (0.2"/hr to 61"/hr

 

 

 

vertical), 0.8 cm/hr to 250 cm/hr horizontal (0.3"/hr to 100"/hr horizontal).

 

 

Keys

16 membrane switches.

 

 

Data Archiving

Media: 100MB ZIP disk drive.

 

 

 

Data Types: Analog points, calculations, discrete status, alarms, diagnostics.

 

 

 

Trends: 4 max. (up to 12 points max. per trend)

 

 

 

Unit Data: 1 (up to 12 points, 10,000 records)

 

 

 

Alarm History: Up to 1600 records

 

 

 

Event History: Up to 1600 records

 

 

 

Diagnostic History: Up to 1600 records

 

 

 

Setpoint Programs: 224 maximum on LS120 floppy disk.

 

 

 

Storage Rate Range: 0.25 to 3600 sec.

 

 

 

Capacity: Automatically calculates storage time based on storage rate.

 

 

Setpoint

Up to 4

 

 

programmers

 

 

2

Video recorder – User Manual

Page 16
Image 16
Honeywell VRX180 user manual Specifications, Physical, Environmental, Attributes