Online Operation Using Menus

 

 

 

 

 

 

 

Table 7-11 Pretune STOPPED Prompts (continued)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

 

 

OUTPUT SIZE

 

 

-100 to +100

 

 

Appears if loop is in Manual. Enter the largest change in

 

 

 

 

 

 

 

 

 

 

output (+ or -), in engineering units, that the process will

 

 

 

 

 

 

 

 

 

 

tolerate. The pretune will initiate and analyze this output

 

 

 

 

 

 

 

 

 

 

change.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SP STEP SIZE

 

 

-100 to +100

 

 

Appears if loop is in Auto. Enter the largest change in

 

 

 

 

 

 

 

 

 

 

setpoint (+ or -), in engineering units, that the process will

 

 

 

 

 

 

 

 

 

 

tolerate. The pretune will initiate and analyze this setpoint

 

 

 

 

 

 

 

 

 

 

change.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

START

 

 

 

 

 

Select to start the pretune function. See Before Starting

 

 

 

 

 

 

 

 

 

 

Pretune below.

 

 

 

 

 

 

 

 

 

 

 

 

 

Before Starting Pretune

Before starting Pretune, configure/adjust the loop as follows:

Auto/Manual: Either mode is acceptable. Changing the loop mode after starting pretune will abort the pretune, causing an error message to appear.

Process Variable: Adjust setpoint or output to bring the process variable to normal operation range. Adjusting or switching setpoints or output after starting pretune will abort the pretune, causing an error message to appear.

Gain/Proportional Band, Reset: Use known good settings. Or, set Gain = 1.0 (PB = 100), Reset = 1.0 and place loop in Manual mode.

Rate: Optional. If OFF, pretune will not calculate a Rate.

Suppress Overshoot: Set to OFF. Pretune may detect changes to the working setpoint and abort. Turn this setting back on after pretune is complete.

After Starting Pretune

After starting the pretune, do not change/adjust the loop mode, loop output, loop setpoint, or operating mode. If you do, the pretune will abort. See Pretune Abort Messages later in this section.

Pretune IDENTIFYING & CALCULATING menus

During IDENTIFYING and CALCULATING status, a TUNE indicator appears on all primary displays (not on menus) for the loop being pretuned.

Table 7-12 Pretune IDENTIFYING & CALCULATING Prompts

 

Prompt

 

 

Definition

 

 

STATUS

 

 

Status Identifying or Calculating. This is a read-only prompt.

 

 

 

 

 

 

 

 

PV

 

 

Current process variable value of the loop being tuned. This

 

 

 

 

 

is a read-only prompt.

 

 

 

 

 

 

 

 

OUTPUT

 

 

Current output value of the loop being tuned. This is a read-

 

 

 

 

 

only prompt.

 

 

 

 

 

 

 

Video Recorder – User Manual

239

Page 253
Image 253
Honeywell VRX180 Before Starting Pretune, After Starting Pretune, Pretune Identifying & Calculating menus, Pretune below