Honeywell VRX180 user manual Program Profiler Prompts

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 204
Image 204

Setpoint Profiler

Table 5-3 Program Profiler Prompts

Prompt

 

Range/Selections

 

Definition

 

DISPLAY LO LIM

 

OFF or number

 

Enter the lower limit for the SP Trend

 

 

 

 

 

display. Allow for the maximum and

 

 

 

 

 

minimum Profiler and PV values.

 

 

 

 

 

 

 

DISPLAY HI LIM

 

OFF or number

 

Enter the upper limit for the SP Trend

 

 

 

 

 

display, allowing for the maximum and

 

 

 

 

 

minimum Profiler and PV values.

 

 

 

 

 

 

 

PV #1

 

OFF, analog parameter, number

 

Program the profiler to monitor a process

 

 

 

 

 

variable. PV #1 is trended on the SP

 

 

 

 

 

Trend display. PV #1 is compared to the

 

 

 

 

 

profiler’s value to determine deviation.

 

 

 

 

 

Excessive deviation between PV #1 and

 

 

 

 

 

profiler value can cause a Hold

 

 

 

 

 

(guaranteed soak).

 

 

 

 

 

 

 

PV #2

 

OFF, analog parameter, number

 

This is an optional PV that can also be

 

 

 

 

 

monitored and can be used to determine

 

 

 

 

 

deviation from profiler value. PV #2 is

 

 

 

 

 

shown on SP Trend display’s Point/Detail

 

 

 

 

 

menu. PV #2 is also trended on SP Trend

 

 

 

 

 

display.

 

 

 

 

 

 

 

START

 

Discrete parameter, 1, 0, or OFF

 

See Start on page 185.

 

 

 

 

 

 

 

RESET/RUN

 

Discrete parameter, 1, 0, or OFF

 

See Reset/Run on page 185.

 

 

 

 

 

 

 

HOLD

 

Discrete parameter, 1, 0, or OFF

 

See Hold on page 186.

 

 

 

 

 

 

 

ADVANCE

 

Discrete parameter, 1, 0, or OFF

 

See Advance on page 186.

 

 

 

 

 

 

 

HOT START

 

Discrete parameter, 1, 0, or OFF

 

See Hot Start on page 186.

 

 

 

 

 

 

 

FAST FORWARD

 

Discrete parameter, 1, 0, or OFF

 

See Fast Forward on page 187.

 

 

 

 

 

 

 

SHUTDOWN

 

Discrete parameter, 1, 0, or OFF

 

See Shutdown on page 188.

 

 

 

 

 

 

 

RAMP INCREMENT

 

Discrete parameter, 1, 0, or OFF

 

See External Ramp Type on page 180.

 

 

 

 

 

 

 

GUARANTEED SOAK

 

Discrete parameter, 1, 0, or OFF

 

See Guaranteed Soak on page 182.

 

 

 

 

 

 

 

HOLD LEVEL/EDGE

 

LEVEL or EDGE

 

Select LEVEL to Hold the profiler while

 

 

 

 

 

the Hold discrete is Level ON, and

 

 

 

 

 

resume Run when the Hold discrete is

 

 

 

 

 

Level OFF.

 

 

 

 

 

Select EDGE to Hold the profiler after the

 

 

 

 

 

Hold discrete changes from OFF to ON,

 

 

 

 

 

and resume Run after the Start discrete

 

 

 

 

 

changes from OFF to ON.

 

 

 

 

 

 

 