Online Operation Using Menus

Table 7-9 Tune Loop Prompts (continued)

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

RESET #1

 

 

0.005-99.99 repeats/minute

 

 

Determines the period of time for a repeat of the proportional

 

 

 

 

 

 

 

 

gain output. Enter a starting value at initial configuration. The

 

 

 

 

 

 

 

 

value may be altered Online for final loop tuning. For loops

 

 

 

 

 

 

 

 

with dual tuning, Reset 1 is the time for the first set of tuning

 

 

 

 

 

 

 

 

parameters. Reset 2 is for the second set. (Variable Reset1

 

 

 

 

 

 

 

 

is available by programming a constant's Destination with

 

 

 

 

 

 

 

 

RS. See Program Constants, Section 4.16.)

 

 

 

 

 

 

 

 

A value of OFF may be entered to allow proportional-only

 

 

 

 

 

 

 

 

control. When turned off, the manual reset value determines

 

 

 

 

 

 

 

 

the loop output at setpoint. Bumpless manual to automatic

 

 

 

 

 

 

 

 

transfer is canceled when proportional only control is

 

 

 

 

 

 

 

 

selected.

 

 

 

 

 

 

 

 

 

 

RATE #1

 

 

0.02-10.00 minutes

 

Modifies the loop output based on the rate of change of the

 

 

 

 

 

 

 

 

process variable. The output is modified by a value that

 

 

 

 

 

 

 

 

assumes the rate of change of the process variable will

 

 

 

 

 

 

 

 

continue for the time period specified. Enter a starting value

 

 

 

 

 

 

 

 

or OFF at the time of configuration. The value may be altered

 

 

 

 

 

 

 

 

Online for final loop tuning. For loops with dual tuning, Rate 1

 

 

 

 

 

 

 

 

is the rate for the first set of tuning parameters. Rate 2 is for

 

 

 

 

 

 

 

 

the second set. (Variable Rate1 is available by programming

 

 

 

 

 

 

 

 

a constant's Destination with RT. Program Constants,

 

 

 

 

 

 

 

 

Section 4.16.)

 

 

 

 

 

 

 

 

 

 

 

PROP. BAND #2

 

 

 

 

 

See GAIN #1

 

 

 

 

 

 

 

 

 

 

 

RESET #2

 

 

 

 

 

See RESET #1

 

 

 

 

 

 

 

 

 

 

RATE #2

 

 

 

 

See RATE #1

 

 

 

 

 

 

 

 

 

 

 

MANUAL RESET

 

 

-100 to +100

 

 

This feature functions only when OFF is configured for the

 

 

 

 

 

 

 

 

loop’s RESET parameter. Enter a value equal to the desired

 

 

 

 

 

 

 

 

loop output when the process variable is at setpoint. This

 

 

 

 

 

 

 

 

allows correction of output to account for load changes to

 

 

 

 

 

 

 

 

bring the process variable up to setpoint.

 

 

 

 

 

 

 

 

 

 

 

SUPPRESS

 

 

YES, NO

 

 

This parameter set to YES limits overshoot of the Setpoint

 

 

OVERSHOOT

 

 

 

 

 

(SP) by the Process Variable (PV) after a disturbance in the

 

 

 

 

 

 

 

 

process such as a load or SP change. Through fuzzy logic,

 

 

 

 

 

 

 

 

the working SP of the control loop is dynamically modified by

 

 

 

 

 

 

 

 

the control algorithm to reduce or eliminate overshoot.

 

 

 

 

 

 

 

 

 

 

 

PRETUNE

 

 

 

 

 

Pretune calculates optimum values for a loop's Proportional

 

 

 

 

 

 

 

 

Band/Gain, Reset and Rate by analyzing the reaction of the

 

 

 

 

 

 

 

 

loop to a "step change" in setpoint or output. After these

 

 

 

 

 

 

 

 

new tuning values have been calculated you have the option

 

 

 

 

 

 

 

 

of applying (installing) or not applying them to a preselected

 

 

 

 

 

 

 

 

tune set of the loop. You can pretune a loop while another

 

 

 

 

 

 

 

 

loop is pretuning.

 

 

 

 

 

 

 

 

See Pretune Loop on page 238.

 

 

 

 

 

 

 

 

 

 

 

SET TIMEBASE

 

 

5 MIN, 15 MIN, 30 MIN,

 

 

Enter the timebase for the time axis of the tuning trend

 

 

 

 

 

1 HR, 2 HR, 4 HR

 

 

display.

 

 

 

 

 

 

 

 

 

 

236