Diagnostic and error messages

Table 9-4 Error Messages (continued)

 

Error

 

 

Description

 

 

User Action

 

 

 

 

 

 

 

 

 

 

 

Trend Has Too Many

 

Data Storage cannot store more than 3 points at 1/4

 

 

Change number of points to be

 

 

Points For Rate Selected

 

second scan rate.

 

 

compatible with scan rate.

 

 

 

 

 

 

 

 

 

 

Type Does Not Exist

 

A function block type was loaded that does not exist.

 

 

Re-program or re-load correctly.

 

 

 

 

 

For example, you loaded a Profile but the unit does

 

 

 

 

 

 

 

 

not have the Profile option.

 

 

 

 

 

 

 

 

 

 

 

 

 

Type Incompatible With

 

Analog output type is different from hardware setting.

 

 

Change programming to be

 

 

Hardware

 

Attempted to assign 6th relay as a DAT function.

 

 

compatible with the hardware or

 

 

 

 

 

 

 

 

vice versa, then reload

 

 

 

 

 

 

 

 

configuration or reconfigure the

 

 

 

 

 

 

 

 

block.

 

 

 

 

 

 

 

 

 

 

Type Requires Hardware

 

Hardware is missing for the programmed analog

 

 

Either ignore the message

 

 

 

 

 

output or discrete output relay.

 

 

knowing that those particular

 

 

 

 

 

 

 

 

points did not get loaded or verify

 

 

 

 

 

 

 

 

configuration and make sure that

 

 

 

 

 

 

 

 

the points that are in the

 

 

 

 

 

 

 

 

configuration match the hardware

 

 

 

 

 

 

 

 

components.

 

 

 

 

 

 

 

 

 

 

Undefined Function Block

 

Internal Error.

 

 

No user action.

 

 

Request

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Value Written to

 

An input has been connected and user has tried to

 

 

Avoid changing connected values.

 

 

Indirected Point

 

write a value to that input. For example, if a control

 

 

 

 

 

 

 

 

loop setpoint is connected to AI1 OV, you will receive

 

 

 

 

 

 

 

 

this message if you try to change the loop setpoint

 

 

 

 

 

 

 

 

online.

 

 

 

 

 

 

 

 

 

 

 

 

 

X Axis Must Increase

 

Appears if AI is custom type or CV is Function

 

 

Re-program Xn < Xn+1.

 

 

 

 

 

Generator and if Xn > Xn+1.

 

 

 

 

 

 

 

 

 

 

 

 

 

X Axis Not Increased

 

Appears if AI is custom type or CV is Function

 

 

Re-program X.

 

 

Enough

 

Generator and if X does not increase by at least

 

 

 

 

 

 

 

 

0.00001.

 

 

 

 

 

 

 

 

 

 

 

 

 

Y Axis Not Increased

 

Appears if AI is custom type or CV is Function

 

 

Re-program Y.

 

 

Enough

 

Generator and if Y does not change by at least

 

 

 

 

 

 

 

 

0.00001.

 

 

 

 

 

 

 

 

 

 

 

 

 