Honeywell VRX180 user manual Free Form Logic Prompts, Neg

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 133
Image 133

Programming Function Blocks and Features

Free Form Logic

Lets you enter up to 64 characters as a custom logic equation (EQ) containing inputs and logical operators. The result of this equation is called “Result”. Result is then processed according to the specified condition type and condition time. The final output is CVn OS. See Figure 4-6.

Inputs

 

 

 

 

A

 

 

 

 

B

 

 

CONDITION

 

C

 

 

 

FREE FORM

 

TYPE

 

D

Result

CVn OS

LOGIC

&

E

 

 

EQUATION

 

CONDITION

 

F

 

 

TIME

 

G

 

 

 

 

H

 

 

 

 

Figure 4-6 Free Form Logic Signal Flow

Table 4-27 describes the Free Form Logic prompts. See Table 4-2 for additional prompts.

Table 4-27 Free Form Logic Prompts

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

EQ

 

*

 

 

Symbol for AND operator

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

Symbol for OR operator

 

 

 

 

 

 

 

 

 

 

 

 

^

 

 

Symbol for XOR operator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEG

 

 

Symbol for NOT operator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A, B, C, D, E, F, G, H

 

 

Symbols for Input A through Input H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

Letter O is the symbol for output CVn OS from the previous

 

 

 

 

 

 

 

 

logic calculation. Use for iterative calculations.

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

One = ON

 

 

 

 

 

 

 

 

 

 

 

0

 

Zero = OFF

 

 

 

 

 

 

 

 

 

 

 

 

( )

 

 

Expressions enclosed by parentheses are evaluated first.

 

 

 

 

 

 

 

 

 

INPUT A - INPUT H

OFF, discrete parameter, 0,

 

 

Up to 8 input sources.

 

 

 

 

1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

 

OFF, discrete parameter, 0,

 

 

Resets the output to OFF (0). Use when using the letter O

 

 

 

 

1

 

 

in equations.

 

 

 

 

 

 

 

 

 

 

 

CONDITION TYPE

 

 

NONE, DELAY, EXTEND,

 

 

See Table 4-20 on page 111.

 

 

 

 

 

PULSE, RT PULSE

 

 

 

 

 

CONDITION TIME

 

 

OFF or number

 

 

Enter number of seconds of condition time. See Table 4-20

 

 

 

 

 

 

 

 

on page 111.

 

Video Recorder – User Manual

119

Page 133
Image 133
Honeywell VRX180 user manual Free Form Logic Prompts, Neg