Setpoint Profiler

Segment #3 Value

Segment #1 Value

Ramp Type = External

Features of this ramp type

*First and last segments must be soaks

*No consecutive ramps or soaks

Ramp segments

Soak segments

Time = amount profile will change toward next soak Value

Time = duration of soak

when the Ramp Increment discrete switches on.

Value = value of soak

Value = not used with ramp segment.

 

 

Segment #2 Time

 

Segment #2 Time

 

Segment #2 Time

Segment #1

Segment #3

Time

Time

Segment #2

Ramp Increment Off-to-On

causes incremental value

Elapsed time

change toward next soak

 

Value

Figure 5-6 External Ramp Type

ATTENTION

External ramp type’s TIME prompt is in engineering units of the PV, not in time units (seconds, minutes, or hours).

To increment toward a lower soak value, enter a positive TIME amount. The Setpoint Profiler “knows” to increment or decrement this amount toward the next soak value.

Video Recorder – User Manual

181

Page 195
Image 195
Honeywell VRX180 user manual External Ramp Type, Ramp Type = External