Setpoint Profiler

Parameter name

 

 

Definition

 

 

Triggered

 

Conditions

 

Result

 

 

 

 

 

 

 

 

by

 

present

 

 

 

 

SHUTDOWN

 

When Shutdown is activated by a discrete

 

Rising

 

Profiler is in

 

Profiler

 

 

 

 

input or by the operator menu, the profiler

 

edge

 

Run, Hold, or

 

jumps to

 

 

 

 

jumps from the batch phase to the shutdown

 

 

 

End

 

BATCH

 

 

 

 

phase of a multiphase profile. The shutdown

 

 

 

 

 

LAST

 

 

 

 

phase begins at the segment defined by the

 

 

 

 

 

SEGMENT

 

 

 

 

parameter BATCH LAST SEGMENT+1.

 

 

 

 

+ 1

 

 

 

 

 

Shutdown is useful when you need to shut

 

 

 

 

 

 

 

 

 

 

 

down your process without waiting for the

 

 

 

 

 

 

 

 

 

 

 

profiler to finish a batch.

 

 

 

 

 

 

 

 

Example

BATCH FIRST SEGMENT, which specifies the start of the batch phase of the profile, is set at Segment 3. The last segment of the batch phase, BATCH LAST SEGMENT, is set at Segment 7. The last segment of the profile is Segment 9. When SHUTDOWN changes from OFF to ON, the profiler will jump to Segment 8, the first segment of the shutdown phase of the profile.

See Figure 5-12 Shutdown

Startup

Segments

Batch

Segments

Shutdown

Segments

 

 

 

 

END (batch)

 

 

 

 

END (shutdown)

BATCH LAST SEGMENT + 1

BATCH FIRST SEGMENT

BATCH LAST SEGMENT

Figure 5-12 Shutdown

RAMP INCREMENT

See External Ramp Type on page 180.

Rising edge

Profiler is in Run mode &

RAMP TYPE of profiler is External

Profiler increments by amount specified by the segment’s TIME.