Honeywell VRX180 Point #12 Storage Mode, Copy Display, Setup, LOW Rate, High Rate, Selectors

Models: VRX180

1 294
Download 294 pages 53.02 Kb
Page 182
Image 182

Programming Function Blocks and Features

Table 4-72 Prompts For Storage Setup Of Trends, Alarms, Events, Diagnostics

 

Prompt

 

 

Range/Selections

 

 

Definition

 

 

POINT #1 -

 

 

Analog or discrete parameter

 

 

Select the data points for the trend.

 

 

POINT #12

 

 

 

 

 

 

 

 

 

 

STORAGE MODE

 

 

CONTIN, BATCH, or NONE

 

 

Continuous storage becomes active immediately upon

 

 

 

 

 

 

 

 

 

 

initialization. Batch storage is controlled by a discrete

 

 

 

 

 

 

 

 

 

 

parameter (see BATCH CONTROL) or by start/stop batch

 

 

 

 

 

 

 

 

 

 

menu item. Batch data may be started and stopped several

 

 

 

 

 

 

 

 

 

 

times in a single file until the file is full. Batch start

 

 

 

 

 

 

 

 

 

 

increments a batch number that is stored along with the

 

 

 

 

 

 

 

 

 

 

data. The batch number may be used for data retrieval and

 

 

 

 

 

 

 

 

 

 

analysis using SDA data analysis software.

 

 

COPY DISPLAY

 

 

 

 

 

 

 

Select this to copy the following Trend 1,2, 3 or 4 Display

 

 

SETUP

 

 

 

 

 

 

 

data to Trend 1,2, 3 or 4 Storage data: Point #1–#12, set

 

 

 

 

 

 

 

 

 

 

display limits, timebase (high rate) selector. Once setup is

 

 

 

 

 

 

 

 

 

 

copied, it can be altered.

 

 

LOW RATE

 

 

Seconds: .5, 1, 2, 3, 4, 5, 6, 7, 8,

 

 

Enter data collection rate. This is how often the data points

 

 

 

 

9, 10, 20, 30, 40, 50

 

 

 

are sampled.

 

 

 

 

 

Minutes: 1, 2, 3, 4, 5, 10, 15, 20,

 

 

 

 

 

 

 

30, 40, 50

 

 

 

 

 

 

 

 

 

 

Hours: 1

 

 

 

 

 

 

 

HIGH RATE

 

 

Seconds: .5, 1, 2, 3, 4, 5, 6, 7, 8,

 

 

Enter data collection rate. This is how often the data points

 

 

 

 

9, 10, 20, 30, 40, 50

 

 

 

are sampled.

 

 

 

 

 

Minutes: 1, 2, 3, 4, 5, 10, 15, 20,

 

 

 

 

 

 

 

30, 40, 50

 

 

 

 

 

 

 

 

 

 

Hours: 1

 

 

 

 

 

 

 

ROLLOVER

 

 

ON, OFF

 

 

 

 

Select ON to continue gathering and storing data after the

 

 

 

 

 

 

 

 

 

 

file becomes full. The new data will replace the oldest data

 

 

 

 

 

 

 

 

 

 

on the disk as it is collected. No warning will be given.

 

 

 

 

 

 

 

 

 

 

Select OFF to stop storage of this data type when the disk

 

 

 

 

 

 

 

 

 

 

space for it becomes full. A “DISK FULL” message will then

 

 

 

 

 

 

 

 

 

 

appear. Data is buffered until a new disk is inserted and

 

 

 

 

 

 

 

 

 

 

initialized.

 

 

SET DISPLAY

 

 

OFF or number

 

 

Enter upper and lower limit values for the trend display for

 

 

LIMITS

 

 

 

 

 

 

 

each point. If OFF then the trend will use the programmed

 

 

 

 

 

 

 

 

 

 

limits for each point.

 

 

HIGH RATE

 

 

SELECTOR

 

 

 

This discrete triggers the high storage rate when ON(1) and

 

 

SELECTORS

 

 

 

 

 

 

 

the low storage rate when OFF.

 

 

 

 

 

CHANGE WITH KEY

 

 

 

This option enables/disables storage rate changes from the

 

 

 

 

 

 

 

 

 

 

Trend display Point/Trend menu. If YES, storage Trend’s

 

 

 

 

 

 

 

 

 

 

high rate will be used when display Trend’s alternate

 

 

 

 

 

 

 

 

 

 

timebase is selected from the Online Point/Trend menu;

 

 

 

 

 

 

 

 

 

 

Storage Trend’s low rate will be used when display Trend’s

 

 

 

 

 

 

 

 

 

 

normal timebase is selected. See Table 6-2, Point/Detail

 

 

 

 

 

 

 

 

 

 

Menu Prompts, Timebase.

 

 

EXTERNAL

 

 

OFF, discrete parameter, 0, 1

 

 

When ON(1), this discrete parameter will allow storage of

 

 

ENABLE

 

 

 

 

 

 

 

the data type; when off storage for the data type will stop.

 

 

 

 

 

 

 

 

 

 

This enable is independent of the storage mode; it does not

 

 

 

 

 

 

 

 

 

 

control batch start/stop.

 

 

SELECT

 

 

FILE

CYCLE

DRYER

 

 

Select a file name to identify the type of data to be stored.

 

 

FILENAME

 

 

PROD

RECORD

TANK

 

 

 

 

 

 

 

 

UNIT

LOOP

REACTR

 

 

 

 

 

 

 

 

CONFIG

KILN

VESSEL

 

 

 

 

 

 

 

 

CALIB

WCHEM

PRESS

 

 

 

 

 

 

 

 

FURNCE

DEMIN

CONTRL

 

 

 

 

 

 

 

 

BATCH

FERMTR

LEHR

 

 

 

 

 

 

 

 

LINE

STRLZR

OVEN

 

 

 

 

 

 

 

 

ZONE

 

 

 

 

 

 

168