Diagnostic and error messages

9.3 Error Messages

Overview

Sometimes errors occur while you are programming or loading a configuration into your instrument. In most cases the instrument displays a descriptive error message. For example, if you try to program a function block incorrectly, the instrument tells you the problem.

Table 9-4 lists these error messages along with a description of each one and what action to take.

Table 9-4 Error Messages

 

Error

 

 

Description

 

 

User Action

 

 

 

 

 

 

 

 

 

 

 

Alarm/Event/Diagnostic burst

 

 

The instrument had an

 

 

Inspect the Alarm Summary/History

 

 

and transitions lost

 

 

Alarm/Event/Diagnostic burst in the controller

 

 

and the Discrete Summary Screen to

 

 

 

 

 

and some transitions were lost.

 

 

resolve any missing or unresolved

 

 

 

 

 

 

 

 

alarms vs their current states. If the

 

 

 

 

 

 

 

 

state transition that was missing was

 

 

 

 

 

 

 

 

an off state it will be matched and

 

 

 

 

 

 

 

 

processed upon the next on-off

 

 

 

 

 

 

 

 

transition of the corresponding alarm.

 

 

 

 

 

 

 

 

 

 

 

Block Phase Greater Than Block

 

 

In Periodic Timer CV, the phase (start time)

 

 

Change Period to greater than phase

 

 

Period

 

 

is greater than the period. For example, the

 

 

(Start Time) or change Start Time to

 

 

 

 

 

start time is 8:00 and the period is 4:00.

 

 

less than Period.

 

 

 

 

 

 

 

 

 

 

 

Channel Does Not Exist

 

 

A channel was loaded that does not exist.

 

 

Verify programming of affected

 

 

 

 

 

For example, you loaded a dual loop

 

 

function block.

 

 

 

 

 

configuration into a single loop instrument.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit Limits Equal

 

 

Indirect circuit low/circuit high limits must be

 

 

Change to unequal limits.

 

 

 

 

 

unequal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Condition Type Out of Range

 

 

Condition Type (Compare, Logic, Free form

 

 

Verify programming of affected

 

 

 

 

 

Logic) is out of range. Probably caused by

 

 

function block.

 

 

 

 

 

someone incorrectly editing the configuration

 

 

 

 

 

 

 

 

file or by a corrupt .LNC file.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Desired F0 Value Not

 

 

In the F0 Sterilization CV, desired F0 is not

 

 

Change F0 value to greater than zero.

 

 

Programmed or Less Than Zero

 

 

programmed or is less than zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Limit Outside of circuit

 

 

AI circuit high limit is > voltage limit of 5200

 

 

Change limit to within specified limits

 

 

 

 

 

mV.

 

 

for that type.

 

 

 

 

 

 

 

 

 

 

 

High Output Limit Greater than

 

 

A current output (CAT) high output limit

 

 

Decrease high limit.

 

 

20

 

 

cannot be greater than 20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hysteresis Less Than Zero

 

 

Alarm Hysteresis parameter should be

 

 

Increase Hysteresis.

 

 

 

 

 

greater than or equal to zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Impulse Time less than or Equal

 

 

Impulse time on a time

 

 

Increase impulse time.

 

 

to 0

 

 

proportioning/duration adjusting output (DAT)

 

 

 

 

 

 

 

 

cannot be less than or equal to zero.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Incompatible Curve Type

 

 

AI is custom type, thermocouple class,

 

 

Reprogram curve so that for all n: Yn

 

 

 

 

 

reference junction enabled but Y values are

 

 

> Yn+1 or Yn < Yn+1

 

 

 

 

 

not always increasing or not always

 

 

 

 

 

 

 

 

decreasing.

 

 

 

 

 

 

 

 

 

 

 

 

 