Displaying SNMP configuration information

4. Advanced Operations

Displaying SNMP configuration information

The Show SNMP command displays all SNMP configuration information.

SNMP support status

SNMP community strings

Trap timer value

Trap destinations

To display SNMP configuration information:

At the Switched PDU: prompt, type show snmp and press Enter.

Example

The following command displays the SNMP configuration information:

Switched PDU: show snmp<Enter>

 

SNMP Configuration

 

SNMP:

Enabled

SET Community String:

private

GET Community String:

public

TRAP Community String:

trap

Error Trap Repeat Time (seconds): 180

Trap Destination 1:

64.42.31.208

Trap Destination 2:

(undefined)

SNMP Traps

The Switched PDU supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or outlet

(O) level.

Trap Summary

Name

Level(s)

Description

Status

T, I, O

Operational status change

 

 

 

Change

O

Control status change

 

 

 

Load

I

Input load out of limit

All traps include the Location of the Switched PDU as defined with the Set Location command. See Creating a location description on page 37 for more information.

Status trap

A Status trap is generated when an error condition occurs on a tower, infeed or outlet. Status traps include the reported Status, the Location of the Switched PDU, and identifier and name of the affected tower, infeed or outlet.

Any Trap Status generates a Status trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Status returns to a non-error status.

Tower Status traps

Status

Error

Description

Normal

 

Tower is working correctly

 

 

 

NoComm

x

Communication to the tower has been lost

Infeed Status traps

Status

Error

Description

On

 

Infeed is on

 

 

 

OffError

x

Infeed should be on but no current is sensed at the infeed

 

 

 

NoComm

x

Communication to the infeed has been lost

 

 