MGE UPS Systems Switched PDU Temp traps, Humidity traps, Advanced Operations, Temp Trap

Models: Switched PDU

1 62
Download 62 pages 5.96 Kb
Page 51
Image 51
Temp Trap

4. Advanced Operations

Temp Trap

The Temp trap is generated whenever the temperature on a temperature/humidity sensor is beyond preset thresholds. Temp traps include the reported temperature, temp status, Location of the Switched PDU, and identifier and name of the affected sensor.

Any error state generates a Temp trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Temp returns to a non-error status.

Temp traps

Status

Error

Description

Normal

 

The sensor is working correctly and the temperature is within preset thresholds

 

 

 

NotFound

 

No sensor has been detected

 

 

 

Reading

 

Temp status currently being read

 

 

 

TempLow

x

Temperature at the sensor below preset low threshold

 

 

 

TempHigh

x

Temperature at the sensor exceeds preset high threshold

 

 

 

ReadError

x

Unable to read Temp status

 

 

 

Lost

x

Sensor initially detected but communication to the sensor has been lost

 

 

 

NoComm

x

Communication to the sensor has been lost

Humidity Trap

The Humidity trap is generated whenever the umidity on a temperature/humidity sensor is beyond preset thresholds. Humidity traps include the reported relative humidity, humidity status, Location of the Switched PDU, and identifier and name of the affected sensor.

Any error state generates a Humidity trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Humidity returns to a non-error status.

Humidity traps

Status

Error

Description

 

 

 

Normal

 

The sensor is working correctly and the relative humidity is within preset thresholds

 

 

 

NotFound

 

No sensor has been detected

 

 

 

Reading

 

Humidity status currently being read

 

 

 

HumidLow

x

Relative humidity at the sensor below preset low threshold

 

 

 

HumidHigh

x

Relative humidity at the sensor exceeds preset high threshold

 

 

 

ReadError

x

Unable to read Humidity status

 

 

 

Lost

x

Sensor initially detected but communication to the sensor has been lost

 

 

 

NoComm

x

Communication to the sensor has been lost

301-0399-4 Rev A. - Page 51

Page 51
Image 51
MGE UPS Systems Switched PDU user manual Temp traps, Humidity traps, Advanced Operations, Temp Trap, Humidity Trap