MGE UPS Systems Switched PDU Outlet Status traps, Environmental Monitor Status traps, Load traps

Models: Switched PDU

1 62
Download 62 pages 5.96 Kb
Page 50
Image 50
Outlet Status traps

4. Advanced Operations

Outlet Status traps

Status

Error

Description

On

 

Outlet is on

 

 

 

Off

 

Outlet is off

 

 

 

OnWait

 

Outlet Status in transition

 

 

 

OffWait

 

Outlet Status in transition

 

 

 

OnError

x

Outlet should be off but current is sensed at the outlet

 

 

 

OffError

x

Outlet should be on but no current is sensed at the outlet

 

 

 

NoComm

x

Communication to the outlet has been lost

 

 

 

OffFuse

x

Outlet should be on but a blown fuse has been detected

Environmental Monitor Status traps

 

Status

Error

Description

 

Normal

 

The Environmental Monitor is working correctly

 

 

 

 

 

NoComm

x

Communication to the Environmental Monitor has been lost

Temperature/Humidity Sensor Status traps

 

Status

Error

Description

 

 

 

 

 

Found

 

The sensor has been detected

 

 

 

 

 

NotFound

 

No sensor has been detected

 

 

 

 

 

Lost

x

Sensor initially detected but communication to the sensor has been lost

 

 

 

 

 

NoComm

x

Communication to the sensor has been lost

NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the Tower Status returns to Normal.

Change trap

The Change trap is generated for all outlet status changes between any on/off conditions. Change traps include the outlet status, Location of the Switched PDU, and identifier and name of the affected outlet. For descriptions of the outlet status types, please refer to the prior table.

Load Trap

The Load trap is generated whenever the total input load on an infeed exceeds a preset threshold. Load traps include the reported input load, load status, Location of the Switched PDU, and identifier and name of the affected infeed.

Any error state generates a Load trap and triggers the trap timer. A new trap is generated at the end of every timer period until the Load returns to a non-error status.

Load traps

Status

Error

Description

Normal

 

Infeed is on and within preset thresholds

 

 

 

NotOn

 

Infeed is off

 

 

 

Reading

 

Non-error state – Load status currently being read

 

 

 

LoadHigh

x

Infeed current load exceeds preset threshold

 

 

 

OverLoad

x

Infeed current load exceeds the measurable range for the infeed

 

 

 

ReadError

x

Unable to read Load status

 

 

 

NoComm

x

Communication to the infeed has been lost

Page 50 - 301-0399-4 Rev A.