MGE UPS Systems Switched PDU Advanced Operations, Setting the Temperature sensor threshold limits

Models: Switched PDU

1 62
Download 62 pages 5.96 Kb
Page 54
Image 54
Setting the Temperature sensor threshold limits

4. Advanced Operations

Setting the Temperature sensor threshold limits

The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold limits for the Temperature sensor.

To set the Temperature threshold limits:

At the Switched PDU: prompt, type set trap ths, templow or temphigh, followed by the sensor name and a value from 0 to 127 in degrees Celsius. Press Enter.

Example

The following command sets the second temperature high threshold limit to 95:

Switched PDU: set trap ths temphigh .a2 95<Enter>

Enabling or Disabling the Humid trap

The Set Trap THS Humid command is used to enable or disable the Humid trap.

To Enable or Disable the Humid trap:

At the Switched PDU: prompt, type set trap ths humid, followed by the sensor name and on or off. Press

Enter.

Example

The following command enables the Humid trap for the first temperature-humidity sensor:

Switched PDU: set traps ths humid .a1 on<Enter>

Setting the Humidity sensor threshold limits

The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper threshold limits for the Humidity sensor.

To set the Humidity threshold limits:

At the Switched PDU: prompt, type set trap ths, humidlow or humidhigh, followed by the sensor name and a value from 0 to 100 in percent relative humidity. Press Enter.

Example

The following command sets the first humidity sensor low threshold limit to 5:

Switched PDU: set trap ths humidlow .a1 5<Enter>

Page 54 - 301-0399-4 Rev A.