SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Generator Power Receptacles

 

 

 

 

 

!

If unit does not have GFCI recep-

 

 

 

 

 

 

tacles, use GFCI-protected extension

 

 

 

 

 

 

cord.

 

 

 

 

 

 

. Generator power decreases as weld

 

 

 

 

 

 

current increases.

 

 

 

 

 

 

Set Fine Control R1 at 10 for full genera-

 

 

 

 

 

 

tor power.

 

 

 

 

 

 

1

240 V 50 A AC Receptacle RC1

 

 

 

 

 

RC1 supplies 60 Hz single-phase power at

 

 

 

 

 

weld/power speed. Maximum output is 10.5

 

 

 

 

 

kVA/kW.

 

 

 

 

 

 

2

120 V 20 A AC Duplex Receptacle

 

 

 

 

 

 

RC2

 

 

 

 

 

 

3

120 V 20 A AC Duplex Receptacle

 

 

 

 

 

 

RC3

 

 

 

 

 

 

RC2 and RC3 supply 60 Hz single-phase

 

 

 

 

 

power at weld/power speed. Maximum out-

 

 

 

 

 

put from RC2 or RC3 is 2.4 kVA/kW.

 

 

 

 

 

4

Supplementary Protector CB1

1

5

2

6

3

CB1 protects receptacles RC1, RC2, and

 

 

 

 

 

RC3 from overload. If CB1 opens, the recep-

 

 

 

 

 

tacles do not work. Place switch in On posi-

 

 

 

 

 

tion to reset.

 

 

 

 

 

 

5

Supplementary Protector CB2

 

 

 

 

 

6

Supplementary Protector CB3

 

 

 

 

 

CB2 protects RC2 and CB3 protects RC3

 

 

 

 

 

from overload. If a supplementary protector

 

 

 

 

 

opens, the receptacle does not work.

 

 

 

 

 

. Press button

to reset supplementary

 

 

 

 

 

 

protector. If

supplementary protector

 

 

 

 

 

 

continues to open, contact Factory

 

 

 

 

 

 

Authorized Service Agent.

 

 

 

 

 

7

Optional 120 V 20 A AC GFCI Recep-

 

 

 

 

 

 

tacles GFCI-2 and GFCI-3

 

 

 

 

 

GFCI2 and GFCI3 supply 60 Hz single-

 

 

 

 

 

phase power at weld/power speed. Maxi-

 

 

 

 

 

mum output from GFCI-2 or GFCI-3 is 2.4

 

 

 

 

 

kVA/kW. Circuit protection is the same as

 

 

 

 

 

standard receptacles.

 

 

 

 

 

If a ground fault is detected, the GFCI Reset

 

 

 

 

 

button pops out and the circuit opens to dis-

 

 

 

 

 

connect the faulty equipment. Check for

 

 

 

 

 

damaged tools, cords, plugs, etc. connected

 

 

 

 

 

to the receptacle. Press button to reset re-

 

4

 

 

 

ceptacle and resume operation.

 

 

 

 

!

Power is still present at the 240 volt

 

 

7

 

 

 

 

 

 

 

receptacle when only one supple-

 

 

 

 

 

 

 

 

 

 

 

 

mentary protector trips.

 

 

 

 

 

 

Unplug power cord before attempting

 

 

 

 

 

 

to service accessories or tools.

 

 

 

 

 

. At least once a month, run engine at

 

 

 

 

 

 

weld/power speed and press Test button

 

 

 

 

 

 

to verify GFCI is working properly.

 

 

 

 

 

Combined output of all receptacles limited to

 

 

 

 

 

10.5 kVA/kW rating of the generator.

 

 

 

 

 

EXAMPLE: If 20 A is drawn from each 120

 

 

 

 

 

V duplex receptacle, only 23 A is available at

 

 

 

 

 

the 240V receptacle:

 

 

 

 

 

2 x (120 V x 20 A) + (240 V x 23 A) = 10.5

 

 

 

 

 

kVA/kW

 

 

 

 

 

 

 

 

803 750-B / Ref. 228 201-B

OM-4419 Page 29