SECTION 6 − OPERATING AUXILIARY EQUIPMENT

6-1. 120 Volt And 240 Volt Duplex Receptacles

1

2

3

YIf unit does not have GFCI receptacles, use GFCI-pro- tected extension cord.

1120 V 15 A AC Receptacle RC2

2240 V 15 A AC Receptacle RC1

Receptacles supply 60 Hz single- phase power at weld/power speed.

3Circuit Breakers CB1 And CB2

CB1 and CB2 protect RC1 and RC2 from overload. If CB1 or CB2 opens, RC1 and one half of RC2 does not work. 120 volts may still be present at RC1. Press button to reset breaker.

.If a circuit breaker continues to

open, contact Factory Autho- rized Service Agent.

Maximum output from each duplex receptacle is 1.8 kVA/kW, and 3 kVA/kW from all receptacles.

.Auxiliary power is not affected by weld output.

EXAMPLE: If 10 A is drawn from RC1, only 5 A is available at RC2:

(240 V x 10 A) + (120 V x 5 A) = 3.0 kVA/kW

Ref. ST-180 933-B