2. Installation Procedure

This section will guide you through installing the Internal and the External SNMP-32 card.

UPS

Internal SNMP

Fig. 3-Internal SNMP-32 Card

Internal SNMP-32 card

NOTE: The SNMP-32 cards are designed to be Hot Swappable, but there is a remote chance that when Hot-Swapping the SNMP-32 card that the UPS will shutdown. MINUTEMAN recommends following steps 1 through 9 when installing the SNMP-32 card, but to hot-swap, skip to step number 3 and omit steps 7, 8.

1.Turn off all the equipment that is plugged into the UPS.

2.Turn off the UPS and unplug the UPS’s power cord from the AC wall outlet.

3.Remove the two retaining screws from the option slots cover plate (rear panel of the UPS).

4.Remove the option slot’s cover plate (rear panel of the UPS).

5.Insert the SNMP-32 card into the option slot and re-install the two retaining screws.

6.Connect the Ethernet cable to the Ethernet Port on the SNMP-32 card.

7.Plug the UPS’s power cord into the AC wall outlet and turn the UPS on.

8.Turn on all the equipment that is plugged into the UPS.

9.Now the SNMP-32 is ready to be Setup (see the Setup Procedure).

UPSPower

Adapter

External SNMP

Serial UPS cable

Fig. 4-External SNMP-32 Card (SNMP-32L Only)

External SNMP-32 card (SNMP-32L Only)

NOTE: The SNMP-32 cards are designed to be Hot Swappable, but there is a remote chance that when Hot-Swapping the SNMP-32 card that the UPS will shutdown. MINUTEMAN recommends following steps 1 through 11 when installing the SNMP-32 card, but to hot-swap, skip to step number 3 and omit steps 9, 10.

1.Turn off all the equipment that is plugged into the UPS.

2.Turn off the UPS and unplug the UPS’s power cord from the AC outlet.

3.Plug the power adaptor’s connector into the connector on the external adaptor box, labeled “Input”.

4.Plug the DB9 Male to Female cable into the connector on the external adaptor box, labeled “To UPS”.

5.Plug the other end of the DB9 Male to Female cable into the Serial Port on the UPS (rear panel of the UPS).

6.Plug the power adaptor into one of the Battery Powered outlets of the UPS.

7.Insert the SNMP-32 card into the option slot and install the two retaining screws.

8.Connect the Ethernet cable to the Ethernet Port on the SNMP-32 card.

9.Plug the UPS’s power cord into the AC wall outlet and turn the UPS on.

10.Turn on all the equipment that is plugged into the UPS.

11.Now the SNMP-32 card is ready to be setup (see the Setup Procedure).