Installing

Server is assigned two valid, static IP addresses: one for the RTC and the other for the E2T card for the 250/700 User Controller. The 100 User requires only one static IP address.

Customer data network information is available (for example DNS server information)

Range of IP addresses from your LAN authority is available - one IP address for each Mitel Networks IP telephone

System fail transfer (SFT) extensions are identified

Feature codes and numbering plans are available

Central Office services are available and in the correct locations.

Note: If the 3300 ICP is part of a cluster, an IP Console telephony keyboard, 4015IP or 4025IP telephone must be assigned a Static IP Address.

Note: An IP Console, 4015IP, or 4025IP telephone in a clustered environment requires a specific Format, Value, and Scope for Options 128 and 129.

Power

Power wiring to the system must conform to the requirements of the local electrical code. The system power is supplied from a commercial ac power supply. Each unit is powered individually.

The system power must meet the following requirements:

The units may share a branch circuit that is dedicated to one system only; the circuit must not be shared with any other equipment.

Each receptacle of the branch circuit should have a rating of 120 V, 60 Hz, 15 A (or 230 V, 50 Hz, 8 A for 230 V systems)

If the total power requirements of the entire system exceed the rating of one branch circuit, individual dedicated branch circuits may be installed for each unit.

Each unit must have one power receptacle that is three-wire type with the ground wire connected to the ground of the electrical system. Do not attempt to defeat the grounding conductor. The receptacle must not be controlled by a switch.

The location of the power receptacle must be accessible so that the system can be un- plugged during maintenance; however, you must ensure that the power cord does not present a hazard to users or pedestrians and that it is protected from accidental removal.

Note: To prevent accidental removal, attach a warning tag to the plug end of the cord.

Uninterruptible Power Supply

We recommend that you install an uninterruptible power supply (UPS) for the server.

Release 3.3

113