FX Series Programmable Controllers

Devices in Detail 4

4.9Timers

FX1S

FX1N

FX2N

FX2NC

Device Mnemonic: T

Purpose: Timed durations

Alias: Timer(s)

T

Available forms: A driven coil sets internal PLC contacts (NO and NC contacts available). Various timer resolutions are possible, from 1 to 100 msec, but availability and quantity vary from PLC to PLC. The following variations are also available:-

Selectable timer resolutions - see page 4-16 Retentive timers - see page 4-17

Timers used in interrupt and ‘CALL’ subroutines - see page 4-18

Devices numbered in: Decimal, i.e T0 to T9, T10 to T19.

Further uses: None

Example device usage:

X0

T20

K123

Available devices:

 

 

 

 

 

 

 

 

Timer Resolution

FX1S

FX1N

FX2N

FX2NC

 

 

100 msec

63

 

200

 

 

 

(T0 - 62)

 

(T0 - 199)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10 msec

\ 31

 

46

 

 

 

(T32 - 62)

 

(T200 - 245)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 msec

1

 

N/A

 

 

 

(T63)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retentive 1 msec

N/A

 

4

 

 

 

 

(T246 - 249)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Retentive 100 msec

N/A

 

6

 

 

 

 

(T250 - 255)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

\Selectable timers taken from the main range of 100 msec timers, see page 4-16.

Timer accuracy:

• See page 4-18.

4-15