FX Series Programmable Controllers

Basic Program Instructions 2

2.8Load Pulse, Load Trailing Pulse

FX1S

FX1N

FX2N

FX2NC

Mnemonic

Function

Format

Devices

Program steps

 

 

Initial logical

 

 

 

 

 

 

 

LDP

operation -

 

 

 

X, Y, M, S, T, C

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(LoaDPulse)

Rising edge

 

 

 

 

 

 

 

 

 

 

 

 

pulse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LDF

Initial logical

 

 

 

 

 

 

 

operation Falling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(LoaD Falling

 

 

 

X, Y, M, S, T, C

2

 

 

/ trailing edge

 

 

 

 

 

pulse)

 

 

 

 

 

 

 

pulse

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program example:

 

 

 

 

 

 

LDP

X0

M100

X1

LDF

X0

Y0

0 LDP X 0

2 OR X 1

3 OUT M 100 4 LDF X 0 6 OUT Y 0

Basic points to remember:

-Connect the LDP and LDF instructions directly to the left hand bus bar.

-Or use LDP and LDF instructions to define a new block of program when using the ORB and ANB instructions (see later sections).

-LDP is active for one program scan after the associated device switches from OFF to ON.

-LDF is active for one program scan after the associated device switches from ON to OFF.

Single Operation flags M2800 to M3071:

• The pulse operation instructions, when used with auxiliary relays M2800 to M3071, only activate the first instruction encountered in the program scan, after the point in the program where the device changes. Any other pulse operation instructions will remain inactive.

This is useful for use in STL programs (see chapter 3) to perform single step operation using a single device.

Any other instructions (LD, AND, OR, etc.) will operate as expected.

For more details please see page 4-5.