FX Series Programmable Controllers

Devices in Detail 4

4.9.4Timers Used in Interrupt and ‘CALL’ Subroutines

FX1S

FX1N

FX2N

FX2NC

If timers T192 to T199 and T246 to T249 are used in a CALL subroutine or an interruption routine, the timing action is updated at the point when an END instruction is executed. The output contact is activated when a coil instruction or an END instruction is processed once the timers current value has reached the preset (maximum duration) value.

Timers other than those specified above cannot function correctly within the specified circumstances.

When an interrupt timer (1 msec resolution) is used in an interrupt routine or within a ‘CALL’ subroutine, the output contact is activated when the first coil instruction of that timer is executed after the timer has reached its preset (maximum duration) value.

4.9.5Timer Accuracy

Timer accuracy can be affected by the program configuration. That is to say, if a timer contact is used before its associated coil, then the timer accuracy is reduced.

The following formulas give maximum and minimum errors for certain situations. However, an average expected error would be approximately;

1.5 × The program scan time

Condition 1:

The timer contact appears after the timer coil.

X10

T0

T0

Maximum timing error:

2 × Scan time + The input filter time

Minimum timing error:

Input filter time - The timer resolution

Condition 2:

 

 

 

The timer contact appears before the timer coil.

T0

 

 

 

 

 

 

 

 

 

 

 

X10

Maximum timing error:

3 × Scan time + The input filter time

Minimum timing error:

Input filter time- The timer resolution

Y10

Y10

T0

Internal timer accuracy:

• The actual accuracy of the timing elements within the PLC hardware is;

±10 pulses per million pulses. This means that if a 100 msec timer is used to time a sin- gle day, at the end of that day the timer will be within 0.8 seconds of the true 24 hours or 86,400 seconds. The timer would have processed approximately 864,000; 100 msec pulses.

4-18