FX Series Programmable Controllers

Devices in Detail 4

4.10.1 General/ Latched 16bit UP Counters

The current value of the counter increases

each time coil C0 is turned ON by X11. The

output contact is activated when the coil is

turned ON for the tenth time (see diagram).

After this, the counter data remains unchanged

when X11 is turned ON. The counter current

value is reset to ‘0’ (zero) when the RST

instruction is executed by turning ON X10 in

the example. The output contact Y0 is also

reset at the same time.

X10

RST C0 X11

C0

C0K10

Y0

Counters can be set directly using constant K

or indirectly by using data stored in a data

register (ex. D). In an indirect setting, the

designation of D10 for example, which

contains the value “123” has the same effect

as a setting of “K123”.

If a value greater than the counter setting is

written to a current value register, the counter

counts up when the next input is turned ON.

This is true for all types of counters.

Generally, the count input frequency should be

around several cycles per second.

X10

X11

0

Y0

1

2

3

4

5

6

7

8

9 10

Battery backed/latched counters:

• Counters which are battery backed/ latched are able to retain their status information, even after the PLC has been powered down. This means on re-powering up, the latched counters can immediately resume from where they were at the time of the original PLC power down.

Available devices:

• Please see the information table on page 4-19.

4-20